Plan Review Notes
Plan Review Notes For Permit 11120073
Permit Number 11120073
Review Stop B
Sequence Number 4
Notes
Date Text
2013-06-17 14:30:31BUILDING PLAN REVIEW
 PERMIT:11120073
 ADD: 700 N CONGRESS
 CONT: TO BE DETERMINED
 CONTACT: VIVEK GALAV
 TEL: (561)644-7416
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
  
 ARCHITECT: REG RICK GONZALEZTEL: 659-2383
 STRUCTURAL ENGINEER: ANDREW MORGAN P. E.
 TEL: 881-8999
 BUILDING PLAN REVIEW
 PERMIT:11120073
 ADD: 700 N CONGRESS
 CONT: TO BE DETERMINED
 CONTACT: JEFF HALVERSONTEL: (561)644-7416
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
  
 ARCHITECT: REG RICK GONZALEZ
 TEL: 659-2383
 STRUCTURAL ENGINEER: ANDREW MORGAN P. E.
 TEL: 881-8999
  
 5TH REVIEW
 DATE: JULY 09/ 2013
 ACTION: PROVISO
  
 BUILDING PROVISO:
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL
 RESULT IN FAILED INSPECTION(S) AND THE ASSESSMENT OF
 RE-INSPECTION FEE(S). REVISIONS REQUIRE ADDITIONAL
 REVIEWS WITH ASSOCIATED FEES.
  
 1) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING& FAC
 RULE 9N-3, PLEASE PROVIDE 2 COPIES OF PRODUCT TESTING
 REPORTS, MISSING REPORTS ARE AS FOLLOWS:
 1A) FIXED GLAZING, STOREFRONT
 1B) OPERABLE GLAZING UNITS
 1C) MULLIONS, HORIZONTAL AND VERTICAL
 1D) GLASS BLOCK
 1E) EXTERIOR GLAZED SWING DOORS
 1F) EXTERIOR INSULATED METAL SWING DOORS
 1G) BI-FOLD APPARATUS BAY DOORS/ WITH TRANSOM
 1H) EXTERIOR ROOF WALL ACCESS DOOR/ FRAME (H)
 1I) DOUBLE ACCESS PANEL ROOF HATCH, INSULATED -182.6.
 1J) WALL LOUVERS
 1K) A/C ROOF TOP A/C STANDS
 1L) ROOF ASSEMBLIES FLAT ROOF INCLUSIVE OF ROOF TOP
 INSULATION.
 1M) ROOF ASSEMBLIES SLOPED ROOF, METAL ROOF SYSTEMS
 -266.9 ZONE 3 AND -372.5 ROOF OVERHANGS WITHIN ZONE# 3.
 1N) BAHAMA SHUTTERS WITH PRODUCT APPROVAL FOR CLOSED
 POSITION AND ENGINEERING ANALYSIS FOR SHUTTERS WHEN
 LEFT IN THE OPEN POSITION IN THE CASE OF A HIGH WIND
 EVENT.
 1O) ROOFTOP EXHAUST FANS
  
 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3) REVISION IS REQUIRED FOR THE DELETION OF STONE
 VENEER ON EXTERIOR WALL OR COMPLIANCE WITH:
 2010 FBC-B 2114.2 CONCRETE BEARING LEDGE.
 BRICK, STONE OR OTHER VENEER SHALL BE SUPPORTED BY A
 CONCRETE BEARING LEDGE AT LEAST EQUAL TO THE TOTAL
 THICKNESS OF THE BRICK, STONE OR OTHER VENEER, WHICH IS
 POURED INTEGRALLY WITH THE CONCRETE FOUNDATION. NO
 SUPPLEMENTAL CONCRETE FOUNDATION POURS WHICH WILL
 CREATE A HIDDEN COLD JOINT SHALL BE USED WITHOUT
 SUPPLEMENTAL TREATMENT IN THE FOUNDATION UNLESS THERE
 IS AN APPROVED PHYSICAL BARRIER. AN APPROVED PHYSICAL
 BARRIER SHALL ALSO BE INSTALLED FROM BELOW THE WALL
 SILL PLATE OR FIRST BLOCK COURSE HORIZONTALLY TO EMBED
 IN A MORTAR JOINT. IF MASONRY VENEER EXTENDS BELOW
 GRADE, A TERMITE PROTECTIVE TREATMENT MUST BE APPLIED
 TO THE CAVITY CREATED BETWEEN THE VENEER AND THE
 FOUNDATION, IN LIEU OF A PHYSICAL BARRIER.
 EXCEPTION: VENEER SUPPORTED BY A SHELF, ANGLE OR LINTEL
 SECURED TO THE FOUNDATION SIDEWALL IN ACCORDANCE WITH
 TMS 402/ACI 530/ASCE 5, PROVIDED AT LEAST A 6-INCH (152
 MM) CLEAR INSPECTION SPACE OF THE FOUNDATION SIDEWALL
 EXTERIOR EXISTS BETWEEN THE VENEER AND THE TOP OF ANY
 SOIL, SOD, MULCH OR OTHER ORGANIC LANDSCAPING
 COMPONENT, DECK, APRON, PORCH, WALK OR ANY OTHER WORK
 IMMEDIATELY ADJACENT TO OR ADJOINING THE STRUCTURE.
 JIM,
 WE WILL REMOVE THE STONE VENEER FROM FIRE STATION 5 AND
 REPLACE IT WITH STUCCO.
 THANKS.
 VIVEK
 ----- FORWARDED BY VIVEK GALAV/WESTPALM ON 06/18/2013
 02:47 PM -----
 FROM: VINCENT KAFER
 TO: "[email protected]"
 DATE: 06/18/2013 11:07 AM
 SUBJECT: FS#5-EOC PERMITTING
 CAN YOU PLEASE PROVIDE A LETTER TO JIM WIETMER
 (BUILDING DEPARTMENT) STATING THAT THE CITY HAS DECIDED
 REMOVING THE STONE VENEER AND REPLACING IT PER STUCCO?
 THANKS
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved