Plan Review Notes For Permit 11120073 |
Permit Number |
11120073 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2013-06-04 10:53:13 | PLANS DENIED | | 1) PROVIDE PRODUCT APPROVALS FOR OUTSIDE LOVERS | | PER SECTION 106.3.3 2007 FBC | | 2) PROVIDE FRESH AIR CALCULATION ON THE PLANS | | PER TABLE 403.3 FBC (M) | | 3) PROVIDE A DETAIL BY THE ENGINEER SHOWING | | CONDENSER STAND TO ROOF TIEDOWN.(BOLT OR SCREW SIZE) | | 4) REFER TO SECTION 306.1 CLEARANCE FOR MAINTENANCE AND | | REPLACEMENT | | FOR VOLUME AND FIRE DAMPERS. | | 5) PROVIDE MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR | | FIRE DAMPERS | | 6) SEPARATE APPLICATION PLANS AND PERMIT REQUIRED FOR | | HOOD, COOLERS & FREEZERS, GENERATOR AND FUEL TANK | | 7) IN RESUBMITTING PLANS REMOVE AND REPLACE ANY PAGES | | AS NECESSARY. | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 |
|