2013-05-14 13:32:01 | FIRE STATION # 5 AND THE EMERGENCY OPERATIONS CENTER |
| 700 NORTH CONGRESS AVENUE |
| PERMIT NUMBER 11120073 |
| |
| 1. SEPARATE PLANS AND PERMITS REQUIRED FO THE DEISEL |
| FUEL TANK, LP GAS TANK, FIRE SPRINKLER AND FIRE ALARM |
| SYSTEMS. |
| |
| 2. LANDSCAPE IS TO BE PLACED SEVERAL FEET AWAY FROM THE |
| BUILDING TO PREVENT PESTS, AND RODENTS FROM ENTERING |
| THE BUILDING. |
| |
| 3. SEVERAL TREES LOCATED ON THE SITE WANT TO BE SAVED. |
| THEY WERE PLANTED BY PERSONNEL AS SAPLINGS AND WANT TO |
| BE SAVED. |
| |
| 4. SEPARATE PLANS AND PERMITS REQUIRED FOR SLIDING GATE |
| DISPLAYED ON PAGE A-0.03. |
| |
| 5. SEPARATE PLANS AND PERMITS REQUIRED FOR ALL LOW |
| VOLTAGE WIRING AND APPURTENANT EQUIPMENT. |
| |
| 6. THERE APPEARS TO BE NO CEILING MOUNTED SPEAKERS IN |
| ROOM 1.28 AND 1.29 AS SHOWN ON PAGE A-2.01. |
| |
| 7. TWO CEILING MOUNTED SPEAKERS SHOWN DIRECTLY NEXT TO |
| ONE ANOTHER IN ROOM 3.20 ON PAGE A-2.01. |
| |
| 8. NO CEILING MOUNTED SPEAKERS DISPLAYED ON SHEET |
| A-2.02 FOR AREA 1.17. |
| |
| 9. ADDRESS NEEDS TO BE DISPLAYED ON ONLY ONE ELEVATION. |
| ON SHEET A-3.01 IT IS DISPLAYED ON WEST AND SOUTH |
| ELEVATIONS. |
| |
| 10. THE GENERATOR INSTALLATION IS TO COMPLY WITH NFPA |
| 110, 37, AND 30. |
| |
| 11. COULD NOT LOCATE A 5.7 ON FLOOR FINISH SCHEDULE ON |
| PAGE A-5.02. |
| |
| 12. ALL FIRE DAMPERS ARE TO BE DROP TESTED AFTER |
| INSTALLATION TO ENSURE PROPER OPERATION. |
| |
| 13. THE FIRE ALARM CONTROL PANEL IS STILL SHOWN IN THE |
| ROOF ELECTRICAL ROOM ON SHEET E-3.03 WHICH IS NOT |
| ACCEPTABLE TO THIS OFFICE. PLEASE RELOCATE THIS PANEL |
| TO THE FIRST FLOOR ELECTRICAL ROOM. |
| |
| 14. SEPARATE PLANS AND PERMITS REQUIRED FOR THE |
| PRE-ACTION SPRINKLER SYSTEM SHOWN ON PAGE FP-7.01. |
| |
| 15. ELECTRONIC SWITCHES ARE REQUIRED ON FIRE-LINE |
| BACKFLOW DEVICES. SEE NOTE # 3 ON SHEET C12. |
| |
| DENIED |
| |
| |
| MICHAEL E. CARSILLO, ASSISTANT FIRE CHIEF |
| WEST PALM BEACH FIRE RESCUE |