Plan Review Notes
Plan Review Notes For Permit 11120073
Permit Number 11120073
Review Stop P
Sequence Number 2
Notes
Date Text
2012-05-09 13:22:00FBC 2007 PLUMBING REVIEW #2
 DENIED:
  
 NO RESPONSE WAS FOUND FOR REVIEW #1:
  
 1. SHEET A-1.06 (1) - SHOWS AN ALUMINUM DOWNSPOUT
 CONCEALED IN A CHASE.
 1A - SHEET A-4.13 & A-416 SHOW ALUMINUM DOWNSPOUT
 UNDERGROUND WITH THE ADAPTER U/G ?
 1B - IF ALUMINUM LEADER LEAKS DOES CHASE FILL WITH
 WATER?
 1C - P-7.01 SHOWS A DOWNSPOUT BOOT DETAIL THAT IS OK
 BUT NOT THE SAME AS A-4.13 - A-4.16, AS IT IS EXPOSED
 OUTSIDE:
 1102.2 INSIDE STORM DRAINAGE CONDUCTORS. INSIDE STORM
 DRAINAGE CONDUCTORS INSTALLED ABOVE GROUND SHALL
 CONFORM TO ONE OF THE STANDARDS LISTED IN TABLE 702.1.
  
 2. A SERARATE RPZ BACKFLOW PREVENTOR OR AIR GAP WILL BE
 REQUIRED FOR THE IRIGATION CISTERN MAKEUP WATER .
  
 4. THE ELEVATOR PUMP WILL BE REQUIRED TO BE PIPED
 INDIRECT INTO THE SANITARY DUE TO THE POSSIBILITY OF
 CONTAMINANTS BEING SENT TO THE GROUND WATER. AN OIL
 SENSOR/PUMP CONTROL/ALARM SYSTEM MAY BE OF HELP IN
 KEEPING OIL OUT OF THE SANITARY SEWER.
 SEC. 90-203. - PROHIBITED DISCHARGES; ILLICIT
 CONNECTIONS. (A)
 GENERAL PROHIBITION. EXCEPT AS PROVIDED IN SECTION
 90-205, AND EXCEPT PURSUANT TO A VALID NPDES PERMIT, IT
 SHALL BE UNLAWFUL FOR ANY PERSON TO DIRECTLY OR
 INDIRECTLY DEPOSIT, DISCHARGE, SPILL, OR DUMP INTO ANY
 OF THE PUBLIC WATERS OR MUNICIPAL SEPARATE STORM SEWER
 SYSTEM WITHIN THE CITY, ANY SUBSTANCE OTHER THAN THAT
 COMPOSED ENTIRELY OF STORMWATER.
  
 5. SHEET P-1.01 - 750 GALLON GREASE TRAP HAS 3" OUTLET
 PIPEING. OUTLET PIPEING SHALL BE 4" MINIMUM:
 1003.5.3 INLET AND OUTLET PIPING. ....THE OUTLET PIPE
 SHALL START AT 8 INCHES (203 MM) ABOVE THE BOTTOM OF
 THE INTERCEPTOR AND EXTEND VERTICALLY TO A TEE. THE TEE
 AND PIPE SHALL BE NO LESS THAN 4 INCHES (102 MM) IN
 DIAMETER. THE TEE SHALL BE INSTALLED WITH THE RUN IN
 THE VERTICAL DIRECTION.
  
 6. SHEET P-1.01 (P-5.01) TRENCH AND FLOOR DRAINS HAVE
 HORIZONTAL DRY VENT UNDER FLOOR:
 905.4 VERTICAL RISE OF VENT. EVERY DRY VENT SHALL RISE
 VERTICALLY TO A MINIMUM OF 6 INCHES (152 MM) ABOVE THE
 FLOOD LEVEL RIM OF THE HIGHEST TRAP OR TRAPPED FIXTURE
 BEING VENTED.
  
 EXCEPTION: VENTS FOR INTERCEPTORS LOCATED OUTDOORS.
 ***NOTE*** THE FLOOR DRAINS CAN BE CONSIDERED
 COMBINATION DRAIN AND VENT, THEREFORE NOT REQUIRING THE
 DRY VENTS UNDER SLAB.
  
 -------------------------------------------------------
 ------------------------------------------------------
 NOTE
 1. ENGINEERING WILL REVIEW WATER STORAGE TANK DUE TO A
 CONCERN OVER A DEAD END SPACE IN THE TANK.
 2. FUEL GAS & LANDSCAPE IRRIGATION ARE NOT PART OF THIS
 REVIEW. SEPARATE PLANS, APPLICATION, FEES, AND PERMIT
 REQUIRED
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  