Plan Review Notes
Plan Review Notes For Permit 11120073
Permit Number 11120073
Review Stop M
Sequence Number 2
Notes
Date Text
2012-05-21 13:24:13PLANS DENIED
 1) PROVIDE PRODUCT APPROVALS FOR ALL OUTSIDE LOVERS .
 PER SECTION 106.3.3 2007 FBC.
 2) PROVIDE FRESH AIR CALCULATIONS ON THE PLANS.
 PER TABLE 403.3 2007 FBC (M) .
 3) PROVIDE A DETAIL ON THE PLANS SHOWING CONDENSER
 STANDS
 TO ROOF TIEDOWN. PER SECTION 3301.12.
 4) REFER TO SECTION 306.1 CLEARANCE FOR MAINTENANCE AND
 REPLACEMENT.
 FOR VOLUME DAMPERS.2007 FBC (M) .
 5) REFER TO SECTION 304.1 GENERAL 2007 FBC (M) PROVIDE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR FIRE
 DAMPERS.
 6) REFER TO SECTION 607.4 ACCESS AND IDENTIFICATION.
 2007 FBC (M) FOR FIREDAMPERS.
 7) SEPARATE APPLICATION AND PLANS REQUIRED FOR HOODS,
 FREEZERS COOLERS
 AND GENERATOR.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]
  
  
  