Plan Review Notes For Permit 11120073 |
Permit Number |
11120073 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2012-05-21 13:24:13 | PLANS DENIED | | 1) PROVIDE PRODUCT APPROVALS FOR ALL OUTSIDE LOVERS . | | PER SECTION 106.3.3 2007 FBC. | | 2) PROVIDE FRESH AIR CALCULATIONS ON THE PLANS. | | PER TABLE 403.3 2007 FBC (M) . | | 3) PROVIDE A DETAIL ON THE PLANS SHOWING CONDENSER | | STANDS | | TO ROOF TIEDOWN. PER SECTION 3301.12. | | 4) REFER TO SECTION 306.1 CLEARANCE FOR MAINTENANCE AND | | REPLACEMENT. | | FOR VOLUME DAMPERS.2007 FBC (M) . | | 5) REFER TO SECTION 304.1 GENERAL 2007 FBC (M) PROVIDE | | MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR FIRE | | DAMPERS. | | 6) REFER TO SECTION 607.4 ACCESS AND IDENTIFICATION. | | 2007 FBC (M) FOR FIREDAMPERS. | | 7) SEPARATE APPLICATION AND PLANS REQUIRED FOR HOODS, | | FREEZERS COOLERS | | AND GENERATOR. | | PLAN REVIEW BY HAROLD MOSER | | 561-805-6732 | | [email protected] | | | | | | |
|