2012-05-23 15:22:58FIRE STATION # 5 AND THE EMERGENCY OPERATIONS CENTER
 (EOC)
 700 NORTH CONGRESS AVENUE
 NEW CONSTRUCTION
 PERMIT # 11120073
  
 1. ON COVER SHEET IT LISTS JONATHAN BRAMLEY AS
 ENGINEERING DIRECTOR. MR. BRAMLEY HAS LEFT THE CITY.
  
 2. SEPARATE PLANS AND PERMITS REQUIRED FOR DIESEL FUEL
 AND LP GAS TANKS.
  
 3. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER SYSTEM. THE FIRE DEPARTMENT CONNECTION (FDC)
 IS TO BE LOCATED WITHIN 150 FEET OF A FIRE HYDRANT.
  
 4. FIRE LINE BACKFLOW DEVICE IS TO BE EQUIPPED WITH
 TAMPER SWITCHES, CHAIN AND LOCK.
  
 5. THE LARGE PAINTING OF THE STATION MASCOT (RHINO) IS
 TO BE SAVED FOR FUTURE USE DURING THE DEMOLITION PHASE
 OF THE PROJECT. THE PAINTING WILL BE INSTALLED IN THE
 NEW FIRE STATION.
  
 6. THE SLIDING GATE WHEN INOPERATIVE, MUST BE ABLE TO
 BE OPENED MANUALLY.
  
 7. EXIT SIGN IS MISSING ON SHEET LS-1 AT THE BOTTOM OF
 THE STAIR 3.51.
  
 8. THE NOTE IN THE CODE ANALYSIS BOX IS INCORRECT. THE
 BUILDING IS EQUIPPPED WITH AN APPROVED FIRE SPRINKLER
 SYSTEM (NFPA 13) NOT (NFPA 75).
  
 9. ON SHEET A-2.01 THERE APPEARS TO BE NUMEROUS CEILING
 MOUNTED SPEAKERS IDENTIFIED AS CS. IN MANYT CASES, THEY
 APPEAR TO BE DIRECTLY NEXT TO ONE ANOTHER.
  
 10. THE NUMBER OF AVAILABLE SLEEPING ACCOMODATIONS WAS
 DISCUSSED WITH ALLAN ORTMAN ON MAY 22, 2012. HE
 EXPLAINED THAT DURING AN ACTUAL EVENT STAFFING WILL BE
 HELD AT A MINIMUM.
  
 11. SMOKE DETECTORS WHEN INSTALLED SHALL BE A MINIMUM
 OF AT LEAST THREE FEET FROM AIR CONDITIONER DIFFUSERS.
  
 12. ON SHEET A-3.01 THE ADDRESS IS ILLUSTRATED ON TWO
 ELEVATIONS. IT IS ONLY NEEDED ON ONE ELVATION.
  
 13. FLOORING CORNERS SHOULD BE ROUNDED WHERE IT MEETS
 WALLS SO CORNERS CAN BE CLEANED.
  
 14. PROVIDE SEPARATE PLANS AND PERMITS FOR ANY CLEAN
 AGENT SYSTEMS PLANNED TO BE INSTALLED.
  
 15. MORE DETAILS NEEDED FOR SECURITY DEVICES PLANNED
 FOR DOORS.
  
 16. THERE APPEARS TO BE NO EMERGENCY LIGHTING IN
 SEVERAL OFFICES ON THE FIRST AND SECOND FLOOR, WHEN
 NORMAL POWER IS LOST. WILL WORK BE ABLE TO BE PERFORMED
 IN THESE AREAS WHEN NORMAL POWER IS LOST.
  
 17. EMERGENCY LIGHTS INSTALLED (GOGGLE EYES) ARE TO BE
 INSTALED AT AN ELEVATION THAT CAN BE TESTED.
  
 18. NO FIRE ALARM DEVICES SHOWN IN VEHICLE BAY ON SHEET
 E-3.01.
  
 19. ON PAGE E-3.03 THE FIRE ALARM CONTROL PANEL IS
 DISPLAYED. A MORE SUITABLE LOCATION IS TO BE PROVIDED
 ON THE FIRST FLOOR AND NOT LOCATED ON THE ROOF LEVEL.
 THE FIRE ALARM SYSTEM IS TO BE MONITORED BY A CENTRAL
 STATION APPROVED FOR CENTRAL STATION SERVICE.
  
 20. PLEASE EXPLAIN PURPOSE OF THE CARD READERS SHOWN ON
 SHEET T-0.02.
  
 21. ALL FIRE DAMPERS AFTER INSTALLATION ARE TO BE DROP
 TESTED TO ENSURE PROPER OPERATION.
  
 22. SOFFITS OR ARCHITECTURAL DETAILS SHALL NOT
 INTERFERE WITH ANY OPERATION OF ANY FIRE SPRINKLER
 HEADS.
  
  
 DENIED
  
  
 MICHAEL E. CARSILLO, ASSISTANT FIRE CHIEF
 WEST PALM BEACH FIRE RESCUE
 804-4707 PHONE
 804-4766 FAX