2012-07-14 13:01:53A SEPARATE SUBMITTAL MUST BE MADE TO:
 ENGINEERING SERVICES DEPARTMENT
 FOR ROW CONSTRUCTION
 401 CLEMATIS ST.
 WEST PALM BEACH, FL 33402
 (561) 494-1098
  
 COMMENTS APPLICABLE TO ON-SITE:
 #1 CISTERN TANK FILL MUST HAVE AN AIR GAP. PROVIDE
 DETAIL.
 #2 PROVIDE MEP DRAWINGS REFERENCED IN CIVIL AND
 MECHANICAL PLANS, THESE PLANS SHOULD PROVIDE DETAIL OF
 FUEL TANKS, DRAINAGE TANK, SANITARY TANKS, AND CORRECT
 PIPING LOCATIONS AND CLEARANCES.
 #3 MECHANICAL PLAN STILL SHOWS NOTES PLACED WHERE OLD
 BUILDING ORIENTATION OF ELEMENTS WHERE.
 #4 HANDICAP PARKING DETAIL IS MISSING SOME DIMENSIONS.
 #6 CHANGE COVER SHEET: DIRECTOR OF ENGINEERING IS
 DANIELLE E. SLATERPRYCE, P.E.
 DIRECTOR ENGINEERING SERVICES & PUBLIC WORKS (REMOVE
 MR. JONATHAN BRAMLEY)
 #7 CONCRETE EXPANSION JOINTS NEED TO BE NOTED ON PLANS
 FOR CONCRETE PARKING AREAS.
 #8 SITE WILL CONSIST OF ALL CONCRETE DRIVE AND PARKING
 AREAS. ON SHEET C6 ALL DETAILS IDENTIFY ASPHALT, REMOVE
 ALL DETAILS NOT REQUIRED.
 #9. TAPS FOR FIRE, DOMESTIC AND CISTERN BACK-UP
 (IRRGATION) MUST BE INDIVIDUALLY TAPPED OFF WATERMAIN
 ON HANK AARON DRIVE. HYDRANT ALSO. CONFIRM WITH FIRE
 DEPARTMENT TO SEE IF THEY DON'T NEED A PRIVATE HYDRANT
 ON-SITE. SOMETIMES THEY REQUIRE ONE FOR TRAINING
 PURPOSES.
 #10 GREASE SEPARATOR DOES NOT SHOW CONNECITON TO THE
 SEWER. SHOW ON CIVIL SHEET C10.
 #11 PROVIDE STRUCTURAL WALL DETAIL FOR WALL ALONG THE
 EAST PERIMETER OF THE PROPERTY.
  
  
  
  
  