2011-12-20 12:44:34FBC 2007 PLUMBING REVIEW #1
 DENIED:
  
 1. SHEET A-1.06 (1) - SHOWS AN ALUMINUM DOWNSPOUT
 CONCEALED IN A CHASE.
 1A - SHEET A-4.13 & A-416 SHOW ALUMINUM DOWNSPOUT
 UNDERGROUND WITH THE ADAPTER U/G ?
 1B - IF ALUMINUM LEADER LEAKS DOES CHASE FILL WITH
 WATER?
 1C - P-7.01 SHOWS A DOWNSPOUT BOOT DETAIL THAT IS OK
 BUT NOT THE SAME AS A-4.13 - A-4.16, AS IT IS EXPOSED
 OUTSIDE:
 1102.2 INSIDE STORM DRAINAGE CONDUCTORS. INSIDE STORM
 DRAINAGE CONDUCTORS INSTALLED ABOVE GROUND SHALL
 CONFORM TO ONE OF THE STANDARDS LISTED IN TABLE 702.1.
  
 2. A SERARATE RPZ BACKFLOW PREVENTOR OR AIR GAP WILL BE
 REQUIRED FOR THE IRIGATION CISTERN MAKEUP WATER .
  
 4. THE ELEVATOR PUMP WILL BE REQUIRED TO BE PIPED
 INDIRECT INTO THE SANITARY DUE TO THE POSSIBILITY OF
 CONTAMINANTS BEING SENT TO THE GROUND WATER. AN OIL
 SENSOR/PUMP CONTROL/ALARM SYSTEM MAY BE OF HELP IN
 KEEPING OIL OUT OF THE SANITARY SEWER
  
 5. SHEET P-1.01 - 750 GALLON GREASE TRAP HAS 3" OUTLET
 PIPEING. OUTLET PIPEING SHALL BE 4" MINIMUM:
 1003.5.3 INLET AND OUTLET PIPING. ....THE OUTLET PIPE
 SHALL START AT 8 INCHES (203 MM) ABOVE THE BOTTOM OF
 THE INTERCEPTOR AND EXTEND VERTICALLY TO A TEE. THE TEE
 AND PIPE SHALL BE NO LESS THAN 4 INCHES (102 MM) IN
 DIAMETER. THE TEE SHALL BE INSTALLED WITH THE RUN IN
 THE VERTICAL DIRECTION.
  
 6. SHEET P-1.01 (P-5.01) TRENCH AND FLOOR DRAINS HAVE
 HORIZONTAL DRY VENT UNDER FLOOR:
 905.4 VERTICAL RISE OF VENT. EVERY DRY VENT SHALL RISE
 VERTICALLY TO A MINIMUM OF 6 INCHES (152 MM) ABOVE THE
 FLOOD LEVEL RIM OF THE HIGHEST TRAP OR TRAPPED FIXTURE
 BEING VENTED.
  
 EXCEPTION: VENTS FOR INTERCEPTORS LOCATED OUTDOORS.
 ***NOTE*** THE FLOOR DRAINS CAN BE CONSIDERED
 COMBINATION DRAIN AND VENT, THEREFORE NOT REQUIRING THE
 DRY VENTS UNDER SLAB.
 -------------------------------------------------------
 -------------------------------------------------------
 -------------------------------------------------------
 ------------------------------
 NOTE
 1. ENGINEERING WILL REVIEW WATER STORAGE TANK DUE TO A
 CONCERN OVER A DEAD END SPACE IN THE TANK.
 2. FUEL GAS & LANDSCAPE IRRIGATION ARE NOT PART OF THIS
 REVIEW. SEPARATE PLANS, APPLICATION, FEES, AND PERMIT
 REQUIRED
  