Plan Review Notes
Plan Review Notes For Permit 11120073
Permit Number 11120073
Review Stop M
Sequence Number 1
Notes
Date Text
2012-01-03 13:54:13PLANS DENIED
 1) PROVIDE PRODUCT APPROVALS FOR ALL OUTSIDE LOVERS PER
 SECTION 106.3.3 2007 FBC.
 2) PROVIDE FRESH AIR CALCULATIONS ON THE PLANS PER
 TABLE 403.3 . 2007 FBC (M)
 3) PROVIDE DUCT SIZE FOR RETURN AIR ON THE PLANS. NECK
 SIZE ON AIR DISTRIBUTION SCHEDULE
 PAGE M-6.01 AND THE PLANS DO NOT MATCH.
 4) SHOW RATED WALLS ON THE MECHANICAL PLANS.
 5) PROVIDE A DETAIL ON THE PLANS FOR THE CONDENSER
 STAND TO ROOF TIE DOWN,
 A THE CONDENSER TO STAND TIE DOWN. PER SECTION 301.12
 FBC (M) 2007
 6) PROVIDE ON THE PLANS THE LOCATION AND TERMINATION OF
 THE GENERATOR
 EXHAUST PIPE.
 7) PROVIDE A DETAIL FOR ACCESS DOORS FOR VOLUME DAMPERS
 ON THE PLANS.
 PER SECTION 603.17 2007 FBC (M)
 8) PROVIDE MANUFACTURER'S INSTALLATION INSTRUCTIONS ON
 THE FIRE DAMPERS. PER SECTION
 607.2 2007 FBC (M) . REFER TO SECTION B607.4 ACCESS AND
 IDENTIFICATION.
 9) PROVIDE ENERGY CALCULATIONS WITH THE PLANS.
 10 PROVIDE EQUIPMENT SCHEDULE FOR IT ROOM AND MIS DATA
 ROOM ON THE PLANS
 11 REFER TO SECTION 304.10 GUARDS FOR CONDENSERS ON
 ROOF.
 12 SEPARATE APPLICATION PLANS AND PERMIT REQUIRED FOR
 HOOD & COOLERS.