Plan Review Notes For Permit 11120073 |
Permit Number |
11120073 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2012-01-03 13:54:13 | PLANS DENIED | | 1) PROVIDE PRODUCT APPROVALS FOR ALL OUTSIDE LOVERS PER | | SECTION 106.3.3 2007 FBC. | | 2) PROVIDE FRESH AIR CALCULATIONS ON THE PLANS PER | | TABLE 403.3 . 2007 FBC (M) | | 3) PROVIDE DUCT SIZE FOR RETURN AIR ON THE PLANS. NECK | | SIZE ON AIR DISTRIBUTION SCHEDULE | | PAGE M-6.01 AND THE PLANS DO NOT MATCH. | | 4) SHOW RATED WALLS ON THE MECHANICAL PLANS. | | 5) PROVIDE A DETAIL ON THE PLANS FOR THE CONDENSER | | STAND TO ROOF TIE DOWN, | | A THE CONDENSER TO STAND TIE DOWN. PER SECTION 301.12 | | FBC (M) 2007 | | 6) PROVIDE ON THE PLANS THE LOCATION AND TERMINATION OF | | THE GENERATOR | | EXHAUST PIPE. | | 7) PROVIDE A DETAIL FOR ACCESS DOORS FOR VOLUME DAMPERS | | ON THE PLANS. | | PER SECTION 603.17 2007 FBC (M) | | 8) PROVIDE MANUFACTURER'S INSTALLATION INSTRUCTIONS ON | | THE FIRE DAMPERS. PER SECTION | | 607.2 2007 FBC (M) . REFER TO SECTION B607.4 ACCESS AND | | IDENTIFICATION. | | 9) PROVIDE ENERGY CALCULATIONS WITH THE PLANS. | | 10 PROVIDE EQUIPMENT SCHEDULE FOR IT ROOM AND MIS DATA | | ROOM ON THE PLANS | | 11 REFER TO SECTION 304.10 GUARDS FOR CONDENSERS ON | | ROOF. | | 12 SEPARATE APPLICATION PLANS AND PERMIT REQUIRED FOR | | HOOD & COOLERS. | | PLAN REVIEW BY HAROLD MOSER | | 561-805-6732 | | [email protected] | | | | |
|