 VERIFY THE GENERATOR SERVICE DISCONNECT IS SERVICE
 RATED AND IS GROUNDED FAULT PROTECTED (GFP) OR HAS A
 GFP INDICATOR. SEE NEC 701.17
 THE ELECTRICAL PLAN IS UNCLEAR AS TO THE CLASSIFICATION
 OF THE IT ROOMS UNDER THE ELECTRIC CODE. NEC 645.4
 THE ELECTRICAL PLAN IS UNCLEAR AS TO THE CLASSIFICATION
 OF THE PREMISES WIRING UNDER THE ELECTRIC CODE FOR
 CRITICAL OPERATIONS POWER SYSTEMS (COPS). NEC 708
 THE PLANS ARE UNCLEAR AS TO HOW THE IT ROOMS ARE TO BE
 VENTILATED. NEC 645.4, 480.9
 PROVIDE A LABELING SCHEDULE FOR THE SAFETY SIGNAGE
 REQUIRED FOR THE ELECTRICAL EQUIPMENT AND ELECTRICAL
 ROOMS. NEC 110.22, 110.16, 701.9
 IDENTIFY THE MINIMUM WIRING METHOD PROPOSED IN ALL
 CLASS 1 DIVISION 2 AREAS. NEC 501.10(B), 501.15(B)
 ELECTRICAL CIRCUITS AND LIGHTING POLES HAVE NOT BEEN
 SPECIFIED FOR THE SITE LIGHTING.
 ELECTRICAL CIRCUITS SERVING LIVING AND SLEEPING AREAS
 REQUIRE AFCI PROTECTION. NEC 210.12, 210.8
  
 NOTE: SEPARATE PERMITS ARE REQUIRED FOR THE LIGHTNING
 PROTECTION SYSTEM, SITE LIGHTING, AUDIO, SECURITY, DATA
 AND PHONES.
  