Plan Review Notes For Permit 11120036 |
Permit Number |
11120036 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-12-01 16:49:14 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | 1- FLAT ROOF: | | A) NOA 07-0730.03 SUBMITTED WAS SUPERSEDED BY | | MIAMI-DADE. PLEASE VISIT THE MIAMI-DADE WEBSITE | | DOWNLOAD CURRENT NOA AND PROVIDE 2 NEW COPIES. | | | | B) PLEASE CLARIFY WHICH APPROVED FLAT ROOF ASSEMBLY IS | | GOING TO BE INSTALLED. TWO DIFFERENT APPROVED | | ASSEMBLIES WERE SUBMITTED. ONE SHOWN ON PAGE 6 OF 18 IS | | FOR AN INSULATED ASSEMBLY. AND, THE OTHER ASSEMBLY | | SHOWN ON PAGE 17 OF 18 IS FOR A NON-INSULATED ASSEMBLY. | | PLEASE SELECT ONLY ONE ASSEMBLY TAKE INTO CONSIDERATION | | IF INSTALLING INSULATION AND TYPE OF FASTENINGS TO BE | | USED. | | | | C) PROVIDE RAS CALCULATIONS FOR NAIL ENHANCING AT | | PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL | | LIMITATION #7 ON LAST PAGE OF NOA SUBMITTED. NEED THE | | NAIL ENHANCING TO MEET THE DESIGN PRESSURES REQUIRED BY | | SEC. R301.2.1.4.3. WHEN DOING THE CALCULATIONS PLEASE | | TAKE INTO CONSIDERATION THAT ACCORDING TO THE 2009 | | REVISIONS THIS BUILDING IS LOCATED IN EXPOSURE "C". SEE | | SEC. R301.2.1.4.3. | | | | 2- SHINGLES: NOA 07-1120.14 SUBMITTED WAS SUPERSEDED BY | | MIAMI-DADE. PLEASE VISIT THE MIAMI-DADE WEBSITE | | DOWNLOAD CURRENT NOA AND PROVIDE TWO NEW COPIES. | | | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 | | [email protected] |
|