2012-01-09 15:51:09400 NORTH CONGRESS AVENUE - SUITE #220
 PERMIT #11110707
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 A SINGLE MEANS OF EGRESS (COMMON PATH OF TRAVEL) IS
 LIMITED TO 75 FEET OF TRAVEL IN AN UNSPRINKLERED
 BUSINESS OCCUPANCY. THE TRAVEL DISTANCE NEEDS TO BE
 MEASURED ALONG THE CENTERLINE OF THE NATURAL PATH OF
 TRAVEL AND CURVING AROUND ANY CORNERS OR OBSTRUCTIONS,
 WITH A 12-INCH CLEARANCE THEREFROM. RECONFIGURE TRAVEL
 DISTANCES USING CRITERIA STATED. INDICATE TRAVEL
 DISTANCE FROM ROOM #208 AND #209. TRAVEL DISTANCE NEEDS
 TO BE MEASURED TO THE FIRE-RATED STAIR ENCLOSURE. ALSO,
 A FIRE EVENT AT CUSTOMER SERVICE #221.1 WOULD FORCE
 OCCUPANTS IN THE BREAK ROOM TO USE THE CORRIDOR AS THE
 NATURAL PATH OF EGRESS.
  
 NO FIRE ALARM CONSTRUCTION DOCUMENTS SUBMITTED WITH
 DRAWING PACKAGE. THE NEW CONFIGURATION OF DOORS AND
 WALLS MAY REQUIRE NOTIFICATION APPLIANCES TO BE ADDED
 OR RELOCATED.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 MODIFICATION OF THE FIRE ALARM SYSTEM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW