Date |
Text |
2011-12-01 14:58:56 | 400 NORTH CONGRESS AVENUE - SUITE #220 |
| PERMIT #11110707 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS |
| OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE |
| REMOVED FROM THE SITE DAILY. |
| |
| FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF |
| THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY. |
| |
| PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| |
| **THE TWO EXIT DOORS (#200 & #217) DO NOT MEET THE |
| REQUIRED SEPARATION DISTANCE OF THE LIFE SAFETY CODE. |
| EXITS SHALL BE SPACED AT LEAST ONE-HALF THE DIAGONAL |
| DISTANCE OF THE FLOOR PLAN. |
| |
| INSUFFICIENT EXIT SIGNS PROVIDED TO ALERT OCCUPANTS OF |
| TWO SEPARATE PATHS OF EGRESS. |
| |
| INDICATE HOW THE LOCK/LATCH WILL BE RELEASED FROM THE |
| EGRESS SIDE OF THE DOORS. |
| |
| PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| EXIT SIGNS. |
| |
| PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL |
| BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. |
| |
| NO EMERGENCY LIGHTING INDICATED ON PLANS. |
| |
| NO FIRE ALARM CONSTRUCTION DOCUMENTS SUBMITTED WITH |
| DRAWING PACKAGE. |
| |
| SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE |
| MODIFICATION OF THE FIRE ALARM SYSTEM. |
| |
| WESLEY JOLIN |
| WEST PALM BEACH FIRE RESCUE |
| FIRE & LIFE SAFETY PLAN REVIEW |
| |