2011-12-20 12:01:18 | BUILDING PLAN REVIEW |
| PERMIT: 11110707 |
| ADD: 400 N CONGRESS # 220 |
| CONT: ROBB CONSTRUCTION |
| TEL: (561) 346-9509 |
| |
| 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) PLEASE REVIEW SHEET LS1.1 DESIGN STANDARDS AND CODE |
| REQUIREMENTS. THE REQUIREMENTS UNDER COMMON PATH OF |
| TRAVEL THE EXCEPTION # 2. THE CODE EXCEPTION READS |
| WHERE A TENANT SPACE HAS AN OCCUPANT LOAD OF NOT |
| GREATER THAN 30, YOUR TENANT SPACE HAS AN OCCUPANT LOAD |
| OF 40. I AGREE THAT THE CORRIDORS SERVING ROOMS 201- |
| 209 DOES HAVE AN OCCUPANT LOAD LESS THAN 30 BUT THE |
| TENANT SPACE DOES HAVE AN OCCUPANT LOAD OF 40 AND THE |
| CODE SECTION INDICATES THE OCCUPANT LOAD OF THE TENANT |
| SPACE. |
| |
| 2) IN NOT BEING ABLE TO MEET THE REQUIREMENTS OF 1014.3 |
| EXCEPTION 2 WE WILL NEED TO REVIEW 1015.1 EXIT ACCESS. |
| WHEN 1015.1.2 COMMON PATH OF TRAVEL CAN NOT BE MET THEN |
| THE REQUIREMENTS OF EXIT ACCESS CORRIDORS NEED TO BE |
| REVIEWED AND THE REQUIREMENT FOR TWO EXITS AND THEIR |
| ARRANGEMENT 1015.1.2.1. IN SHORT IF A FIRE BREAKS OUT |
| LETS SAY IN ROOM 202 WILL THE OCCUPANTS IN THE OTHER |
| OFFICES BE ABLE TO USE THE DOOR # 213 FOR EGRESS |
| PURPOSES? |
| |
| 3) ANOTHER CONCERN IS DOOR # 213 AND NOTE # 1 DOOR |
| SCHEDULE ON A3.1 INDICATING TO VERIFY ALL HARDWARE |
| REQUIREMENTS WITH OWNERS. 11-4.13.9. |
| |
| 4) SHEET A1.1 & A4.1 INDICATE OPENINGS WITHIN CORRIDOR |
| 222 & 223 PLEASE PROVIDE OPENING PROTECTION FOR THESE |
| OPENINGS IN COMPLIANCE WITH FBC-B TABLE 715.4. |
| |
| 5) 712.6 FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, |
| SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL |
| REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE |
| EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR |
| STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY |
| HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE |
| ANY DECORATIVE CEILING AND IN CONCEALED SPACES. |
| SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: "FIRE |
| AND SMOKE BARRIER - PROTECT ALL OPENINGS." |
| |
| 6) PLEASE PROVIDE CODE COMPLIANCE WITH: 712.3 |
| FIRE-RESISTANCE-RATED WALLS. PENETRATIONS INTO OR |
| THROUGH FIRE WALLS, FIRE-BARRIER WALLS, SMOKE-BARRIER |
| WALLS AND FIRE PARTITIONS SHALL COMPLY WITH SECTIONS |
| 712.3.1 THROUGH 712.3.4. |
| |