Plan Review Notes
Plan Review Notes For Permit 11110642
Permit Number 11110642
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2011-12-12 14:00:51340 CLEMATIS STREET - SUITE #101
 PERMIT #11110642
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE AN OCCUPANT LOAD BASED UPON THE NEW SEATING
 LAYOUT. EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED
 SEATS SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED
 IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE
 ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT CONNECTION
 OF THE SPRINKLER SYSTEM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW