Plan Review Notes
Plan Review Notes For Permit 11110642
Permit Number 11110642
Review Stop E
Sequence Number 1
Notes
Date Text
2011-12-01 09:02:1311110642
 340 CLEMATIS ST.
 INTERIOR RENOVATION
  
 PROVIDE AN ELECTRICAL PLAN WITH A PANEL SCHEDULE
 SHOWING RATING, SIZE AND WIRING METHOD FOR THE NEW
 ELECTRICAL CIRCUITS. NEC 210.3
  
 ALL RECEPTACLES LOCATED WITH IN SIX FEET OF A SINK MUST
 BE GFCI PROTECTED. NEC 210.8
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  
  