Plan Review Notes
Plan Review Notes For Permit 11110627
Permit Number 11110627
Review Stop B
Sequence Number 2
Notes
Date Text
2012-04-13 10:02:222007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE LIVE LOAD FOR THE BALCONY IS REQUIRED TO BE 100
 PSF BY FBC TABLE 1607.1 (5) & (16). PLEASE REVISE SHEET
 A1 AND VERIFY DECK DESIGN FOR 100 PSF LIVE LOAD.
  
 2) FBC 1009.4 REQUIRES STAIRWAY LANDINGS TO HAVE A
 MINIMUM DIMENSION MEASURED IN THE DIRECTION OF TRAVEL
 EQUAL TO THE WIDTH OF THE STAIRWAY. PLEASE CORRECT.
  
 3) SHOW COMPLIANCE WITH FBC 1013.2 HEIGHT. GUARDS SHALL
 FORM A PROTECTIVE BARRIER NOT LESS THAN 42 INCHES (1067
 MM) HIGH, MEASURED VERTICALLY ABOVE THE LEADING EDGE OF
 THE TREAD, ADJACENT WALKING SURFACE OR ADJACENT
 SEATBOARD.
 NOTE: FBC 1012.2 HEIGHT. HANDRAIL HEIGHT, MEASURED
 ABOVE STAIR TREAD NOSINGS, OR FINISH SURFACE OF RAMP
 SLOPE SHALL BE UNIFORM, NOT LESS THAN 34 INCHES (864
 MM) AND NOT MORE THAN 38 INCHES (965 MM). EXCEPTION:
 HANDRAILS FOR STAIRS NOT REQUIRED TO BE ACCESSIBLE THAT
 FORM PART OF A GUARDRAIL MAY BE 42 INCHES (1067 MM)
 HIGH. BECAUSE THESE STAIRS ARE NOT REQUIRED TO COMPLY
 WITH ACCESSIBILITY, THE STAIR HANDRAILS CAN BE THE TOP
 OF THE GUARDS AT A HEIGHT OF 42". HOWEVER THE 36" SHOWN
 ON THE PLANS IS NOT ALLOWED. PLEASE CORRECT.
  