2012-01-09 10:33:39 | 2007 FBC W/2009 REVISIONS |
| |
| DENIED BY BUILDING |
| |
| 1) SPECIFY THE USE, OCCUPANCY TYPE, NUMBER OF UNITS AND |
| OCCUPANT LOAD ON THE PLANS. FBC 302 |
| |
| 2) SPECIFY THE CONSTRUCTION TYPE OF THE BUILDING THAT |
| THE STAIRS ARE SERVING ON THE PLANS. SEE FBC 602 AND |
| 1009.5. |
| |
| 3) SPECIFY THE 2007 FLORIDA BUILDING CODE AND THE |
| DESIGN PARAMETERS ON THE PLANS PER FBC 1603.1. SPECIFY |
| THE FLOOR LIVE LOAD FOR THE STAIRS, LANDING AND |
| BALCONY, AS WELL AS THE WIND DESIGN DATA. |
| |
| 4) SHOW COMPLIANCE WITH 1604.1 FOR STRUCTURAL DESIGN |
| AND A CONTINUOUS LOAD PATH. |
| |
| 5) SUBMIT TWO COPIES OF A SURVEY THAT INDICATES THE |
| DISTANCE TO OTHER STRUCTURES LOCATED ON THE PROPERTY |
| AND TO THE PROPERTY LINES. SEE FBC 701. |
| |
| 6) SPECIFY THE STAIRWAY WIDTH ON THE PLANS. SHOW |
| COMPLIANCE WITH FBC 1009.1. |
| |
| 7) PLEASE CLARIFY THE NUMBER OF STAIR STRINGERS ON THE |
| PLANS. IT IS SPECIFIED AS 2 IN ONE PLACE AND 3 IN |
| ANOTHER. |
| |
| 8) SPECIFY THE STAIR TREAD AND RISER DIMENSIONS ON THE |
| PLANS. SHOW COMPLIANCE WITH FBC 1009.3. |
| |
| 9) SPECIFY THE NUMBER OF STEPS AND THE TOTAL VERTICAL |
| RISE OF THE STAIRS. SEE FBC 1009.6 VERTICAL RISE. |
| |
| 10) SPECIFY THE STAIR LANDING DIMENSIONS ON THE PLANS, |
| SHOWING THAT THEY COMPLY WITH FBC 1009.4. |
| |
| 11) SHOW COMPLIANCE WITH FBC 1013 FOR THE REQUIRED |
| GUARDS AT THE BALCONY, LANDING AND STAIRS. SHOW |
| COMPLIANCE FOR HEIGHT, OPENING LIMITATIONS AND |
| STRENGTH. |
| |
| 12) SHOW COMPLIANCE WITH FBC 1009.10 FOR THE REQUIRED |
| HANDRAILS. |
| |
| 13) SHOW COMPLIANCE WITH FBC 1012 FOR HEIGHT AND |
| GRASPABILITY AND FBC 1607.7 FOR STRENGTH AND ATTACHMENT |
| REQUIREMENTS. |
| |
| 14) SHOW COMPLIANCE WITH FBC 1012.5 FOR HANDRAIL |
| EXTENSIONS WHERE HANDRAILS ARE NOT CONTINUOUS BETWEEN |
| FLIGHTS. |
| |
| 15) IF REQUIRED TO BE ACCESSIBLE, HANDRAILS SHALL |
| COMPLY WITH FBC 11-4.26.2. |
| |