2011-11-30 16:07:43 | BUILDING PLAN REVIEW |
| PERMIT: 11110625 |
| ADD: 3720 S DIXIE HWY SUITE B |
| CONT: FOX VALLEY BUILDING CORP |
| TEL: (561)282-8281 |
| |
| 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) PLEASE REVIEW THE PERMIT APPLICATION ADDRESS FIELD |
| AND PLANS. BOTH INDICATE THE JOB LOCATION TO BE AT 3720 |
| N DIXIE WHILE THE PROPERTY CONTROL NUMBER SUBMITTED IS |
| FOR 3720 S DIXIE? 106.1.2 ADDITIONAL INFORMATION IS |
| REQUIRED. |
| |
| 2) THE SECOND ISSUE IS THIS A SINGLE TENANT SPACE FOR |
| TWO TENANTCIES? PLEASE PROVIDE IF TWO SEPERATE |
| TENANTCIES WHAT TYPE OF BUSINESSES WILL BE IN EACH, |
| DEPENDING ON THIS INFORMATION EITHER TENANT SEPERATION |
| WALLS MAY BE REQUIRED PER SECTION FBC-B 708.1 OR |
| OCCUPANCY SEPERATION WALLS PER FBC-B TABLE 508.3.3. |
| |
| 3) IF THIS RECONFIGURATION OF SPACE IS TWO SEPERATE |
| TENANTS THEN THE TENANT SEPERATION WALL SHOULD CONTINUE |
| TO THE ROOF DECK ABOVE. FBC-B 708.1. |
| |
| 4) THE PLANS ALSO INDICATE BY DETAIL THE NEW SECTION OF |
| INTERIOR WALL, PLEASE REVIEW CEILING INSULATION CAN NOT |
| LAY ON THE DROP IN CEILING TILE. FBC-B 13.404.AB.1. |
| |
| 5A) THE PLANS DO HAVE TWO BUILDING VIOLATIONS THE |
| KITHEN DOOR BLOCKS EGRESS WITHIN THIC CORRIDOR. |
| FBC-B1008.1.8.8. |
| |
| 5B) THE PLANS ALSO SHOW THE DOUBLE DOORS AT THE |
| VESTIBULE ENTRY BEING BLOCKED BY THE SWING OF A ENTRY |
| DOOR INTO THE NEWLY FORMED SPACE. |
| |
| 6) MAY REQUIRE: BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| |