Plan Review Notes For Permit 11110609 |
Permit Number |
11110609 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-11-29 11:52:32 | 306 CLEMATIS STREET | | PERMIT #11110609 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | AN ADDITIONAL MONITOR MODULE IS NEEDED FOR THE BACKFLOW | | PREVENTER. | | | | ONE HORN/STROBE APPLIANCE IS INSUFFICIENT FOR THE MAIN | | RETAIL SPACE. | | | | PER LOCAL CODE AMENDMENTS, DUCT SMOKE DETECTORS SHALL | | INITIATE A GENERAL FIRE ALARM CONDITION. | | | | NOTE: FIRE ALARM CIRCUIT BREAKER TO BE MARKED IN RED | | AND IDENTIFIED AS "FIRE ALARM." PROVIDE CIRCUIT BREAKER | | LOCK FOR DEDICATED BRANCH CIRCUIT. | | | | WESLEY JOLIN | | WEST PALM BEACH FIRE RESCUE | | FIRE & LIFE SAFETY PLAN REVIEW | | |
|