2011-11-29 11:52:32306 CLEMATIS STREET
 PERMIT #11110609
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 AN ADDITIONAL MONITOR MODULE IS NEEDED FOR THE BACKFLOW
 PREVENTER.
  
 ONE HORN/STROBE APPLIANCE IS INSUFFICIENT FOR THE MAIN
 RETAIL SPACE.
  
 PER LOCAL CODE AMENDMENTS, DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM CONDITION.
  
 NOTE: FIRE ALARM CIRCUIT BREAKER TO BE MARKED IN RED
 AND IDENTIFIED AS "FIRE ALARM." PROVIDE CIRCUIT BREAKER
 LOCK FOR DEDICATED BRANCH CIRCUIT.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  