| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| *****PROVISO***** |
| |
| PROVIDE AN ARCHITECTURAL SEATING AND FURNITURE PLAN. |
| |
| EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS |
| SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A |
| CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM. |
| SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF |
| OCCUPANTS PERMITTED FOR EACH ROOM. |
| |
| EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE |
| PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING |
| FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS |
| SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN |
| WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 |
| FEET ON CENTER. |
| |
| PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL |
| BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. PROVIDE |
| DETAILS. |
| |
| DEEP FAT FRYERS SHALL BE EQUIPPED WITH A SEPARATE |
| HIGH-LIMIT CONTROL IN ADDITION TO THE ADJUSTABLE |
| THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN THE FAT |
| TEMPERATURE REACHES 475F DEGREES AT 1-INCH BELOW THE |
| SURFACE. |
| |
| STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS |
| CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO |
| THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS |
| 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED |
| REFLECTIVE COLOR AND BEAR THE LETTER R DESIGNATION PER |
| FLORIDA STATUTE 633.027 AND FLORIDA ADMINISTRATIVE CODE |
| 69A-60.0081. |
| |
| PER CONVERSATION WITH ARCHITECT (1/5/12) OUTDOOR |
| SEATING AREA DOES NOT HAVE A CEILING, ONLY A SMALL ROOF |
| OVERHANG. NOTE: NO AWNING, CEILING, ROOF OR ANY OTHER |
| STRUCTURE THAT WILL ALLOW SMOKE TO ACCUMULATE IS TO BE |
| INSTALLED OVER THE OUTDOOR DINING AREA. |
| |
| WESLEY JOLIN |
| WEST PALM BEACH FIRE RESCUE |
| FIRE & LIFE SAFETY PLAN REVIEW |