Plan Review Notes
Plan Review Notes For Permit 11110598
Permit Number 11110598
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2012-01-04 15:22:371700 SOUTH DIXIE HIGHWAY
 PERMIT #11110598
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO*****
  
 PROVIDE AN ARCHITECTURAL SEATING AND FURNITURE PLAN.
  
 EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS
 SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A
 CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM.
 SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF
 OCCUPANTS PERMITTED FOR EACH ROOM.
  
 EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER.
  
 PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL
 BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. PROVIDE
 DETAILS.
  
 DEEP FAT FRYERS SHALL BE EQUIPPED WITH A SEPARATE
 HIGH-LIMIT CONTROL IN ADDITION TO THE ADJUSTABLE
 THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN THE FAT
 TEMPERATURE REACHES 475F DEGREES AT 1-INCH BELOW THE
 SURFACE.
  
 STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS
 CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO
 THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS
 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED
 REFLECTIVE COLOR AND BEAR THE LETTER R DESIGNATION PER
 FLORIDA STATUTE 633.027 AND FLORIDA ADMINISTRATIVE CODE
 69A-60.0081.
  
 PER CONVERSATION WITH ARCHITECT (1/5/12) OUTDOOR
 SEATING AREA DOES NOT HAVE A CEILING, ONLY A SMALL ROOF
 OVERHANG. NOTE: NO AWNING, CEILING, ROOF OR ANY OTHER
 STRUCTURE THAT WILL ALLOW SMOKE TO ACCUMULATE IS TO BE
 INSTALLED OVER THE OUTDOOR DINING AREA.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW