2012-01-05 18:13:20****PROVISOS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. SEPARATE PERMIT REQUIRED FOR ROOF. PRODUCT APPROVALS
 TO BE REVIEWED BY DESIGNER OF RECORD PRIOR TO
 SUBMITTAL, FBC106.3.3. THE ASSEMBLY PROPOSED IS TO BE
 INDICATED AND CALCULATIONS FOR ZONES 2 AND 3, IF
 REQUIRED, ARE TO BE SUBMITTED. PRESSURES TO COMPLY WITH
 MINIMUM REQUIREMENTS SPECIFIED BY EOR ON SHEET S302
 (ZONE 2 -71.7, ZONE 3 -107.9, ZONE 2 OH -61.5, ZONE 3
 OH -101.4).
  
 2. FBC 1008.1.9 AND 1008.1.8.3 ITEM 2, DOOR 103 AND
 REAR GATE TO INCLUDE REQUIRED PANIC HARDWARE; FRONT
 MAIN ENTRY TO EITHER INCLUDE PANIC HARDWARE OR IS TO
 COMPLY WITH EXCEPTION.
  
 3. BUILDING TYPE IIIB REQUIRES A 2 HOUR EXTERIOR
 BEARING WALL, SEE FBC TABLE 601. EITHER REVISE PLAN TO
 SHOW COMPLIANCE OR REVISE BUILDING TYPE EITHER WITH A
 REVISION OR A LETTER. PROPOSED CONSTRUCTION APPEARS TO
 COMPLY WITH TYPE VB.
  
 4. PROVIDE A SOILS INVESTIGATION REPORT, FBC 1802.2.1
 PRIOR TO FOOTING INSPECTION.
  
  
  