Plan Review Notes For Permit 11110598 |
Permit Number |
11110598 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2012-01-05 18:13:20 | ****PROVISOS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | 1. SEPARATE PERMIT REQUIRED FOR ROOF. PRODUCT APPROVALS | | TO BE REVIEWED BY DESIGNER OF RECORD PRIOR TO | | SUBMITTAL, FBC106.3.3. THE ASSEMBLY PROPOSED IS TO BE | | INDICATED AND CALCULATIONS FOR ZONES 2 AND 3, IF | | REQUIRED, ARE TO BE SUBMITTED. PRESSURES TO COMPLY WITH | | MINIMUM REQUIREMENTS SPECIFIED BY EOR ON SHEET S302 | | (ZONE 2 -71.7, ZONE 3 -107.9, ZONE 2 OH -61.5, ZONE 3 | | OH -101.4). | | | | 2. FBC 1008.1.9 AND 1008.1.8.3 ITEM 2, DOOR 103 AND | | REAR GATE TO INCLUDE REQUIRED PANIC HARDWARE; FRONT | | MAIN ENTRY TO EITHER INCLUDE PANIC HARDWARE OR IS TO | | COMPLY WITH EXCEPTION. | | | | 3. BUILDING TYPE IIIB REQUIRES A 2 HOUR EXTERIOR | | BEARING WALL, SEE FBC TABLE 601. EITHER REVISE PLAN TO | | SHOW COMPLIANCE OR REVISE BUILDING TYPE EITHER WITH A | | REVISION OR A LETTER. PROPOSED CONSTRUCTION APPEARS TO | | COMPLY WITH TYPE VB. | | | | 4. PROVIDE A SOILS INVESTIGATION REPORT, FBC 1802.2.1 | | PRIOR TO FOOTING INSPECTION. | | | | | | |
|