Plan Review Notes For Permit 11110598 |
Permit Number |
11110598 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-12-08 11:59:50 | ****CORRECTIONS**** | | 11110598 | | | | 1. SEPARATE PERMITS AND REVIEWS REQUIRED FOR | | REFRIGERATION EQUIPMENT, HOOD. | | | | 2. GUARDS REQUIRED WHERE MECHANICAL EQUIPMENT IS | | LOCATED LESS THAN 10FT FROM ROOF EDGE, FBC MECHANICAL | | 304.10. | | | | 3. FD (FIRE DAMPERS) SHOWN AT UNITS 3, 4, 5 BUT NO WALL | | IS IN THESE LOCATIONS. | | | | 4. VOLUME DAMPERS REQUIRED, FBC MECHANICAL 603.1.7. | | | | 5. DUCT SMOKE DETECTORS REQUIRED, FBC MECHANICAL 606.2. | | | | 6. SUPERVISION REQUIRED FOR DUCT SMOKE DETECTORS, FBC | | MECHANICAL 606.4.1. | | | | HAROLD MOSER, CHIEF MECHANICAL INSPECTOR | | 561-805-6732 | | | | | | |
|