Plan Review Notes
Plan Review Notes For Permit 11110598
Permit Number 11110598
Review Stop M
Sequence Number 1
Notes
Date Text
2011-12-08 11:59:50****CORRECTIONS****
 11110598
  
 1. SEPARATE PERMITS AND REVIEWS REQUIRED FOR
 REFRIGERATION EQUIPMENT, HOOD.
  
 2. GUARDS REQUIRED WHERE MECHANICAL EQUIPMENT IS
 LOCATED LESS THAN 10FT FROM ROOF EDGE, FBC MECHANICAL
 304.10.
  
 3. FD (FIRE DAMPERS) SHOWN AT UNITS 3, 4, 5 BUT NO WALL
 IS IN THESE LOCATIONS.
  
 4. VOLUME DAMPERS REQUIRED, FBC MECHANICAL 603.1.7.
  
 5. DUCT SMOKE DETECTORS REQUIRED, FBC MECHANICAL 606.2.
  
 6. SUPERVISION REQUIRED FOR DUCT SMOKE DETECTORS, FBC
 MECHANICAL 606.4.1.
  
 HAROLD MOSER, CHIEF MECHANICAL INSPECTOR
 561-805-6732
  
  
  