2011-12-08 14:41:02 | 1700 SOUTH DIXIE HIGHWAY |
| PERMIT #11110598 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS |
| OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE |
| REMOVED FROM THE SITE DAILY. |
| |
| PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET. |
| NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT |
| LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND SHALL |
| CONTRAST THE BACKGROUND COLOR. ADDRESS TO FACE DIXIE |
| HIGHWAY. |
| |
| PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY |
| RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING |
| NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM |
| WWW.KNOXBOX.COM. |
| |
| THE BENCH TYPE SEATING COUNT NEEDS TO BE FIGURED INTO |
| THE OCCUPANT LOAD CALCULATIONS. |
| |
| BOTH THE INDOOR AND OUTDOOR AREAS EXCEED AN OCCUPANT |
| LOAD OF 50 PERSONS AND WILL REQUIRE TO TWO SEPARATE, |
| DISTINCT EXITS. THE EXIT DISCHARGE OF THE OUTDOOR |
| DINING EXIT LEADS BACK TO THE MAIN BUILDING ENTRANCE |
| AND CANNOT BE CONSIDERED A SEPARATE EXIT. |
| |
| PROVIDE THE ARCHITECTURAL SEATING PLAN THAT IS BEING |
| UTILIZED IN THE ENGINEERING DRAWINGS. |
| |
| PORTABLE FIRE EXTINGUISHERS SHALL HAVE A MINIMUM RATING |
| OF 2A:10BC AND SHALL BE TAGGED BY A LICENSED FIRE |
| EXTINGUISHER COMPANY. |
| |
| PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| EXIT SIGNS. |
| |
| FOR OCCUPANCIES WITH AN OCCUPANT LOAD OF 100 OR MORE |
| PERSONS, PANIC HARDWARE SHALL BE PROVIDED ON DOORS TO |
| RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR LATCHES ARE |
| PERMITTED THAT WOULD NOT BE RELEASED BY THE PANIC |
| HARDWARE. AS A SUBSTITUTE FOR PANIC HARDWARE, THE MAIN |
| ENTRANCE IS PERMITTED TO HAVE AN INTERIOR KEYED DOOR |
| LOCK (AND NO LATCH) WITH A READILY VISIBLE SIGN STATING |
| THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING IS |
| OCCUPIED. SIGN LETTERS SHALL BE AT LEAST 1 INCH IN |
| HEIGHT. A THUMB TURN STYLE LOCK IS NOT PERMITTED TO BE |
| SUBSTITUTED FOR A KEYED LOCK. |
| |
| EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS |
| SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A |
| CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM. |
| SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF |
| OCCUPANTS PERMITTED FOR EACH ROOM. |
| |
| EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE |
| PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING |
| FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS |
| SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN |
| WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 |
| FEET ON CENTER. |
| |
| PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL |
| BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. |
| |
| INDICATE THE HOURLY FIRE RATING OF THE FIRE DOORS. FIRE |
| DOORS SHALL BE SELF CLOSING AND POSITIVE LATCHING. |
| |
| DEEP FAT FRYERS SHALL BE EQUIPPED WITH A SEPARATE |
| HIGH-LIMIT CONTROL IN ADDITION TO THE ADJUSTABLE |
| THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN THE FAT |
| TEMPERATURE REACHES 475F DEGREES AT 1 INCH BELOW THE |
| SURFACE. |
| |
| SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE FIRE |
| SPRINKLER SYSTEM, KITCHEN EXHAUST HOOD, AND HOOD |
| SUPPRESSION SYSTEM. |
| |
| FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY AN APPROVED |
| SUPERVISING STATION IN ACCORDANCE WITH NFPA 72. |
| |
| WESLEY JOLIN |
| WEST PALM BEACH FIRE RESCUE |
| FIRE & LIFE SAFETY PLAN REVIEW |
| |