Plan Review Notes For Permit 11110516 |
Permit Number |
11110516 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-12-01 10:41:11 | 11110516 | | 333 CLEMATIS ST. | | INTERIOR RENOVATION | | | | VERIFY THAT ALL NEW AND EXISTING EQUIPMENT INTENDED TO | | INTERRUPT CURRENT AT FAULT LEVELS HAS AN INTERRUPTING | | RATING SUFFICIENT FOR THE NOMINAL CIRCUIT VOLTAGE AND | | CURRENT THAT IS AVAILABLE AT THE LINE TERMINALS OF THE | | EQUIPMENT. NEC 110.9 | | VERIFY THE EXISTING SERVICE RISER HAS ADEQUATE SIZE AND | | CLEARANCE. NEC 230.24 | | INDICATE THE WIRE SIZE REQUIRED FOR THE SERVICE RISER. | | NEC 310.16 | | VERIFY THAT ALL MAIN SERVICE DISCONNECTS ARE GROUPED IN | | ONE LOCATION. SHOW SERVICE LOCATION ON THE PLAN. NEC | | 230.72 | | SHOW ALL SERVICE GROUNDING AND BONDING. NEC 215.5 | | PROVIDE A LIGHTING PLAN. SPECIFY ON THE PLANS HOW THE | | LIGHTING WILL BE CONTROLLED USING MOTION SENSORS OR | | SIMILAR TECHNIQUES AS REQUIRED BY THE FLORIDA BUILDING | | CODE. SPACE CONTROL FBC 13-415 ABC.1.2; ADDITIONAL | | CONTROLS 13-415.ABC.1.3, EXISTING BUILDING 711.1 | | IF THERE ARE SHOW WINDOWS AT LEAST ONE RECEPTACLE | | OUTLET IS REQUIRED AT THE TOP OF THE SHOW WINDOWS FOR | | EACH 12 LINEAR FEET. NEC 210.63 | | PROVIDE A SIGN CIRCUIT. NEC 660.5 | | | | ROBERT LECKY | | COMMERCIAL COMBINATION PLANS EXAMINER | | [email protected] | | 561-805-6718 | | | | |
|