2011-11-21 16:02:11REROOF REVISION BUILDING REVIEW COMMENTS.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- ENGINEER TO PROVIDE RAS 117 CALCULATIONS FOR THE
 CORNER AREAS. ACCORDING TO SEC. 10.4.5 OF RAS 117 ALL
 CALCULATIONS NEED TO BE ROUNDED DOWN TO THE NEXT WHOLE
 NUMBER NOT ROUNDED UP. MY CALCULATIONS SHOW THAT
 FASTENER SPACING FOR CORNER AREAS IS LESS THAN 8" O.C..
 PLEASE REVISE CALCULATIONS AS REQUIRED.
  
 2- FLAT ROOF PRODUCT APPROVAL SUBMITTED IS DIFFERENT
 FROM THE ONE APPROVED AT THE TIME OF PERMIT ISSUANCE.
 PLEASE, PROVIDE COMPLETE FLORIDA PRODUCT APPROVAL. ONLY
 PAGE 5 WAS SUBMITTED AT THIS TIME.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER