Plan Review Notes For Permit 11110429 |
Permit Number |
11110429 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-12-13 11:25:33 | PLANS DENIED | | MISSING TWO SMOKE DAMPERS IN HALL # 6 PAGE M1.1 ON | | PLANS | | REFER TO SECTION 606.2.1 SUPPLY AIR SYSTEMS AND SECTION | | 606.4.1 SUPERVISION | | 2007 FBC (M) | | PLAN REVIEW BY HAROLD MOSER | | 561-805-6732 | | [email protected] | | | | | | |
|