2011-11-18 11:30:35777 SOUTH FLAGLER DRIVE - SUITE #1600W
 PERMIT #11110378
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE SUITE NUMBER ON PLANS.
  
 THE BILL OF MATERIALS INDICATE THE MORTISE LOCKSET IS
 FAIL SECURE. LOCKS SHALL BE FAIL SAFE ALONG THE PATH OF
 EGRESS.
  
 PLANS INDICATE TWO REQUEST TO EXIT BUTTONS; PLEASE
 EXPLAIN THIS FEATURE. THE HARDWARE FOR OCCUPANT RELEASE
 OF THE LOCK IS REQUIRED TO BE AFFIXED TO THE DOOR LEAF.
  
 PLANS INDICATE DOORS ARE FREE EGRESS; PLEASE EXPLAIN
 WHY LOCKS WOULD THEN BE TIED INTO THE FIRE ALARM
 SYSTEM.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  