Plan Review Notes For Permit 11110378 |
Permit Number |
11110378 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-11-18 11:30:35 | 777 SOUTH FLAGLER DRIVE - SUITE #1600W | | PERMIT #11110378 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | PROVIDE SUITE NUMBER ON PLANS. | | | | THE BILL OF MATERIALS INDICATE THE MORTISE LOCKSET IS | | FAIL SECURE. LOCKS SHALL BE FAIL SAFE ALONG THE PATH OF | | EGRESS. | | | | PLANS INDICATE TWO REQUEST TO EXIT BUTTONS; PLEASE | | EXPLAIN THIS FEATURE. THE HARDWARE FOR OCCUPANT RELEASE | | OF THE LOCK IS REQUIRED TO BE AFFIXED TO THE DOOR LEAF. | | | | PLANS INDICATE DOORS ARE FREE EGRESS; PLEASE EXPLAIN | | WHY LOCKS WOULD THEN BE TIED INTO THE FIRE ALARM | | SYSTEM. | | | | WESLEY JOLIN | | WEST PALM BEACH FIRE RESCUE | | FIRE & LIFE SAFETY PLAN REVIEW | | |
|