 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FILE ROOM DOOR #226 SHALL BE FIRE-RATED FOR 45 MINUTES.
  
 SHEET E1.1: PROVIDE FIRE ALARM NOTIFICATION APPLIANCE
 IN FILES #226.
  
 SHEET E1.1: NO AUDIBLE NOTIFICATION APPLIANCES ARE
 LOCATED IN THE SOUTH EAST PART OF THE FLOOR PLAN. IT
 MAY BE DIFFICULT TO MEET THE AUDIBILITY REQUIREMENTS OF
 NFPA 72 WITH ONLY STROBE DEVICES IN THIS AREA.
  
 NOTE: EXISTING HIGH-RISE BUILDINGS MAY BE REQUIRED TO
 HAVE AN ENCLOSED, PROTECTED ELEVATOR LOBBY PER BUILDING
 CODE OFFICIAL.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW