2011-11-28 15:28:50 | BUILDING PLAN REVIEW |
| PERMIT: 11110283 |
| ADD: 505 S FLAGLER 2ND FLOOR |
| CONT: IBIS BUILDING |
| TEL: (561)307-4951 |
| |
| 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) THE PERMIT APPLICATION INDICATES THE SCOPE OF WORK |
| IS FOR TENANT INTERIOR RENOVATIONS FOR THE 2ND FLOOR. |
| SHEET A-1 INDICATES MORE THAN 50% OF THE FLOOR AREA IS |
| TO BE ALTERED. THIS LEADS US INTO REVIEWING FOR CODE |
| COMPLIANCE FOR ELEVATOR LOBBIES. THE BUILDING OFFICIAL |
| & BATTALION CHIEF HAVE ISSUED A MEMORANDUM IN REGARDS |
| TO REMODELING OF FLOORS IN HIGH RISE BUILDINGS WHERE |
| THE CODES HAVE REQUIRED ELEVATOR LOBBIES OR THEIR |
| EXCEPTIONS SINCE 1929. |
| |
| TO BETTER PREPARE BUILDING OWNERS, MANGERS, OPERATORS, |
| AND DESIGN PROFESSIONALS TO ANTICIPATE AND ADDRESS |
| THESE SPECIFIC CODE REQUIREMENTS, THE CONSTRUCTION |
| SERVICES DEPARTMENT AND FIRE PREVENTION DEPARTMENT |
| PROPOSE TO ADDRESS THE ABSENCE OF AN ELEVATOR LOBBY |
| (WHEN REQUIRED) AS FOLLOWS: |
| |
| 1. IF A TENANT IMPROVEMENT IS SUBMITTED WHICH PROPOSES |
| TO RECONFIGURE THE ENTIRE EXISTING BUILDING FLOOR, AN |
| ELEVATOR LOBBY, OR COMPLIANCE WITH ONE OF THE SIX (6) |
| EXCEPTIONS ALLOWED UNDER THE PRESENT CODE WILL BE |
| REQUIRED. THIS IS REGARDLESS OF WHETHER OR NOT THE |
| ABSENCE OF AN ELEVATOR LOBBY CAN BE DEMONSTRATED WITH A |
| VALID PERMIT ISSUED BETWEEN OCTOBER 1, 2005 AND |
| DECEMBER 8, 2006. |
| 2. IF A TENANT IMPROVEMENT IS SUBMITTED WHICH PROPOSES |
| TO RECONFIGURE A PORTION OF THE EXISTING BUILDING FLOOR |
| AREA, WITH NO WORK BEING PROPOSED IN THE AREA OF THE |
| ELEVATOR LOBBY, AND NO ELEVATOR LOBBY IS FOUND TO EXIST |
| ON THE FLOOR, AND A VALID PERMIT CAN BE EVIDENCED WHICH |
| WAS ISSUED BETWEEN OCTOBER 1, 2005 AND DECEMBER 8, |
| 2006, THE TENANT IMPROVEMENT PERMIT MAY BE APPROVED AND |
| THE BUILDING SHALL REMAIN AS LAWFULLY CONFIGURED UNTIL |
| THE MAJORITY OF THE EXISTING FLOOR PLAN, OR THE |
| ELEVATOR LOBBY AREA ITSELF UNDERGOES RENOVATION. |
| 3. IF A TENANT IMPROVEMENT IS SUBMITTED WHICH PROPOSES |
| TO RECONFIGURE A PORTION OF THE EXISTING BUILDING FLOOR |
| AREA, WITH NO WORK BEING PROPOSED IN THE AREA OF THE |
| ELEVATOR LOBBY, AND NO ELEVATOR LOBBY IS FOUND TO EXIST |
| ON THE FLOOR, AND NO VALID PERMIT CAN BE EVIDENCED |
| WHICH WAS ISSUED BETWEEN OCTOBER 1, 2005 AND DECEMBER |
| 8, 2006, THE TENANT IMPROVEMENT PERMIT MAY BE APPROVED. |
| THE BUILDING OWNER WILL BE NOTIFIED OF AN UNSAFE |
| CONDITION ON THE EXISTING STRUCTURE BY THE CITY FIRE |
| MARSHAL?S OFFICE AND ASKED TO UNDERTAKE APPROPRIATE |
| ACTIONS TO CORRECT THE SITUATION. |
| 4. IF ANY RECONFIGURATION IS PROPOSED WHICH AFFECTS THE |
| ELEVATOR LOBBY AREA ITSELF, AN ELEVATOR LOBBY, OR |
| COMPLIANCE WITH ONE OF THE SIX (6) EXCEPTIONS LISTED IN |
| THE CODE SHALL BE REQUIRED. |
| |
| IT SHOULD BE NOTED THAT CITY STAFF REMAINS COMMITTED TO |
| ASSISTING BUILDING OWNERS, MANAGERS, AND DESIGN |
| PROFESSIONALS IN SUCCEEDING IN CREATING AND MAINTAINING |
| SAFE PLACES TO LIVE AND WORK IN OUR COMMUNITY. WE ARE |
| READY AND WILLING TO PROVIDE TECHNICAL ASSISTANCE IN |
| UNDERSTANDING THE OFTEN COMPLEX CRITERIA THAT AFFECT |
| EXISTING AND NEW HIGH RISE BUILDINGS. IT MUST BE STATED |
| THAT THE SIMPLE INSTALLATION OF A HOIST-WAY |
| PRESSURIZATION SYSTEM MAY BE ONE POTENTIAL METHOD TO |
| ELIMINATE THE NEED FOR AN ELEVATOR LOBBY THROUGHOUT AN |
| ENTIRE BUILDING. ANOTHER ALTERNATIVE IS TO INSTALL FIRE |
| SHUTTERS AT THE ELEVATOR DOOR OPENINGS. THESE |
| METHODOLOGIES MAY OFFER THE ADDED POTENTIAL TO INCREASE |
| THE LEASABLE FLOOR AREA WITHIN THESE BUILDINGS. |
| |
| PLEASE FEEL FREE TO CONTACT US DIRECTLY IF WE CAN |
| ASSIST YOU FURTHER IN UNDERSTANDING THESE CRITERIA AND |
| HELP YOU TO ENSURE THE SAFETY OF YOUR RESIDENTS, |
| TENANTS, AND PROPERTY. |
| |
| DOUG WISE 805-6650 ? [email protected] |
| MIKE CARSILLO 804-4709 ? [email protected] |
| |
| FL BLDG CODE 703.2.2 SUPPLEMENTAL SHAFT AND FLOOR |
| OPENING ENCLOSURE REQUIREMENTS. WHERE THE WORK AREA ON |
| ANY FLOOR EXCEEDS 50 PERCENT OF THAT FLOOR AREA, THE |
| ENCLOSURE REQUIREMENTS OF SECTION 703.2 SHALL APPLY TO |
| VERTICAL OPENINGS OTHER THAN STAIRWAYS THROUGHOUT THE |
| FLOOR. |
| |
| 2) PLEASE PROVIDE COMPLIANCE WITH: FBC-B 712.6 FIRE |
| WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE BARRIERS |
| AND SMOKE PARTITIONS OR ANY OTHER WALL REQUIRED TO HAVE |
| PROTECTED OPENINGS SHALL BE EFFECTIVELY AND PERMANENTLY |
| IDENTIFIED WITH SIGNS OR STENCILING IN A MANNER |
| ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION. SUCH |
| IDENTIFICATION SHALL BE ABOVE ANY DECORATIVE CEILING |
| AND IN CONCEALED SPACES. SUGGESTED WORDING FOR FIRE AND |
| SMOKE BARRIERS: "FIRE AND SMOKE BARRIER - PROTECT ALL |
| OPENINGS." |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |