2011-11-08 12:04:07RESIDENTIAL (R3) REROOF BUILDING REVIEW COMMENTS.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- FLAT ROOF PROPOSED NAIL ENHANCING INDICATES NAILS
 SPACING AT 7"O.C. FOR THE ROOF PERIMETER AREA AND
 6"O.C. FOR THE ROOF CORNER AREAS. IT LOOKS LIKE THE
 ENGINEER ROUNDED UP THE FASTENER SPACING. ACCORDING TO
 SEC. 10.4.5 OF RAS 117, THE FASTENER SPACING NEEDS TO
 BE ROUNDED DOWN NOT UP. ENGINEER TO CLARIFY IF NUMBERS
 WHERE ROUNDED UP OR DOWN. PROVIDE ACTUAL CALCULATIONS
 AND REVISE AS REQUIRED. SEC. 106.1.2 CITY AMENDMENTS TO
 FBC.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATIONS PLANS EXAMINER
 (561)805-6712