Plan Review Notes
Plan Review Notes For Permit 11110112
Permit Number 11110112
Review Stop B
Sequence Number 2
Notes
Date Text
2011-12-19 13:39:58ADDITION/ALTERATION (R3) BUILDING REVIEW COMMENTS.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY RULE 9N-3
 FOR:
 A) 6'-8" FIBERGLASS DOORS AS SHOWN ON PLANS. DRAWING
 FL-11321.6 SUBMITTED IS FOR 8'-0" DOORS.
 B) WINDOW MULLIONS. NOA 10-0819.05 WAS SUPERSEDED BY
 MIAMI-DADE. NEED CURRENT NOA.
 C) MISSING EXTERIOR DOOR NOA 06-0406.11 SPECIFIED ON
 ENGINEER LETTER LISTING REVIEWED PRODUCT APPROVALS.
  
 ***NOTE: PLEASE HAVE HISTORIC APPROVAL PRIOR TO
 SUBMITTAL TO THIS OFFICE.
  
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS. SEC. 106.3.3 CITY AMENDMENTS.
 UPDATE LETTER STATING ALL PRODUCT APPROVALS COVERED
 UNDER THIS REVISION/ADDITION INCLUDING THE ONES THAT
 WERE SUBMITTED ON FIRST SUBMITTAL.
  
 3- FLAT ROOF: PROVIDE RAS 117 CALCULATIONS FOR NAIL
 ENHANCING AT PERIMETER AND CORNER AREAS AS REQUIRED BY
 GENERAL LIMITATION ON LAST PAGE OF NOA 09-0820.11 TO
 MEET THE DESIGN PRESSURES OF SEC. R301.2.1.4.3.
  
 4- PROVIDE STORM SHUTTERS COMPLETE INSTALLATION
 SCHEDULE AND CLEARLY MARK ON SHUTTERS DRAWINGS SPECIFIC
 MOUNTING CONDITIONS AND ANCHOR TYPE AND SPACING TO BE
 USED. THIS APPLIES TO BOTH TYPES OF SHUTTERS SUBMITTED.
 FABRIC SHUTTERS AND STORM PANELS. SEE CITY POLICY FOR
 HURRICANE SHUTTERS REQUIRED INFORMATION.
  
 5- SPECIFY EMERGENCY OVERFLOW SCUPPERS AS REQUIRED BY
 SEC. R903.4.1.
  
 7- SPECIFY HOW THE ROOF GUTTERS WILL DISCHARGE THE RAIN
 WATER A LEAST ONE FOOT AWAY FROM THE STRUCTURE AS
 REQUIRED BY SEC. R320.7.
  
 8- ARCHITECT TO COORDINATE ROOF DRAINS WITH ENGINEER
 NOTE #1 ON DETAIL 1/S1. THERE ARE NOT INTERIOR ROOF
 DRAINS.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712