Date |
Text |
2011-12-19 13:39:58 | ADDITION/ALTERATION (R3) BUILDING REVIEW COMMENTS. |
| 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| |
| 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY RULE 9N-3 |
| FOR: |
| A) 6'-8" FIBERGLASS DOORS AS SHOWN ON PLANS. DRAWING |
| FL-11321.6 SUBMITTED IS FOR 8'-0" DOORS. |
| B) WINDOW MULLIONS. NOA 10-0819.05 WAS SUPERSEDED BY |
| MIAMI-DADE. NEED CURRENT NOA. |
| C) MISSING EXTERIOR DOOR NOA 06-0406.11 SPECIFIED ON |
| ENGINEER LETTER LISTING REVIEWED PRODUCT APPROVALS. |
| |
| ***NOTE: PLEASE HAVE HISTORIC APPROVAL PRIOR TO |
| SUBMITTAL TO THIS OFFICE. |
| |
| 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| ALL PRODUCT APPROVALS. SEC. 106.3.3 CITY AMENDMENTS. |
| UPDATE LETTER STATING ALL PRODUCT APPROVALS COVERED |
| UNDER THIS REVISION/ADDITION INCLUDING THE ONES THAT |
| WERE SUBMITTED ON FIRST SUBMITTAL. |
| |
| 3- FLAT ROOF: PROVIDE RAS 117 CALCULATIONS FOR NAIL |
| ENHANCING AT PERIMETER AND CORNER AREAS AS REQUIRED BY |
| GENERAL LIMITATION ON LAST PAGE OF NOA 09-0820.11 TO |
| MEET THE DESIGN PRESSURES OF SEC. R301.2.1.4.3. |
| |
| 4- PROVIDE STORM SHUTTERS COMPLETE INSTALLATION |
| SCHEDULE AND CLEARLY MARK ON SHUTTERS DRAWINGS SPECIFIC |
| MOUNTING CONDITIONS AND ANCHOR TYPE AND SPACING TO BE |
| USED. THIS APPLIES TO BOTH TYPES OF SHUTTERS SUBMITTED. |
| FABRIC SHUTTERS AND STORM PANELS. SEE CITY POLICY FOR |
| HURRICANE SHUTTERS REQUIRED INFORMATION. |
| |
| 5- SPECIFY EMERGENCY OVERFLOW SCUPPERS AS REQUIRED BY |
| SEC. R903.4.1. |
| |
| 7- SPECIFY HOW THE ROOF GUTTERS WILL DISCHARGE THE RAIN |
| WATER A LEAST ONE FOOT AWAY FROM THE STRUCTURE AS |
| REQUIRED BY SEC. R320.7. |
| |
| 8- ARCHITECT TO COORDINATE ROOF DRAINS WITH ENGINEER |
| NOTE #1 ON DETAIL 1/S1. THERE ARE NOT INTERIOR ROOF |
| DRAINS. |
| |