2011-11-18 17:04:16 | ADDITION/REVISION BUILDING REVIEW COMMENTS. |
| 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| |
| 1- PLEASE PROVIDE ENERGY CALCULATIONS AS REQUIRED BY |
| SEC. N1100.3. |
| |
| 2- PLEASE PROVIDE PRODUCT APPROVAL (2 COPIES) AS |
| REQUIRED BY DCA RULE 9N-3 FOR: |
| A) CASEMENT WINDOWS AS SPECIFIED ON PLANS. |
| B) SINGLE HUNG WINDOWS. NOA 11-0405.10 SUBMITTED WAS |
| SUPERSEDED BY MIAMI-DADE. PLEASE VISIT THE MIAMI-DADE |
| WEBSITE AND DOWNLOAD CURRENT NOA. |
| C) FIBERGLASS EXTERIOR DOOR. FLORIDA PRODUCT APPROVAL |
| FL-11321.6 SUBMITTED IS FOR 8'-0" DOORS. NEED ONE FOR |
| 6'-8" DOORS AS SPECIFIED ON PLANS. |
| D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| PLANS, SECTIONS AND UPLIFT CONNECTOR SCHEDULE. PLEASE, |
| PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL COVER PAGE |
| AND PAGE SHOWING THE SPECIFIED CONNECTOR. |
| E) WINDOW MULLIONS AS SHOWN ON PLANS. AND CLEARLY |
| INDICATE SIZE OF MULLION TO VERIFY COMPLIANCE WITH THE |
| DESIGN PRESSURES OF SEC. R301.2.1.4.3. |
| F) FLAT ROOF. AND, CLEARLY IDENTIFY WHICH APPROVED |
| ASSEMBLY IS GOING TO BE INSTALLED AND PROVIDE RAS 117 |
| CALCULATIONS. CALCULATIONS TO BE SIGNED AND SEALED IF |
| THE PRODUCT APPROVAL SUBMITTED REQUIRES IT. |
| |
| 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS PRIOR |
| TO SUBMITTAL TO THIS OFFICE AS REQUIRED BY SEC. 106.3.3 |
| CITY AMENDMENTS TO FBC. |
| |
| 4- PLEASE HAVE ALL THE REVISED PLANS AND PRODUCT |
| APPROVALS REVIEWED BY HISTORIC FOR APPROVAL PRIOR TO |
| SUBMITTAL TO THIS OFFICE. |
| |
| 5- PLEASE PROVIDE STORM SHUTTERS COMPLETE INSTALLATION |
| SCHEDULE. AND, CLEARLY MARK ON SHUTTERS DRAWINGS |
| SPECIFIC WALL MOUNTING CONDITIONS (EX: WALL MOUNTED |
| SECTION 1 OR WALL MOUNTED SECTION 2, ETC.), ANCHOR TYPE |
| AND SPACING TO VERIFY COMPLIANCE WITH THE DESIGN |
| PRESSURES BY SEC. R301.2.1.4.3. |
| |
| 6- PLEASE BRING REVISED PLANS TO PALM BEACH COUNTY TO |
| VERIFY IF IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS |
| AND COPY OF PAID RECEIPT IF FEES ARE DUE. |
| |
| 7- PLEASE SPECIFY TYPE OF EXISTING BEDROOM WINDOWS TO |
| BE REPLACED (EX: CASEMENT, SINGLE HUNG, ETC) TO VERIFY |
| COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. R310. |
| |
| 8- ARCHITECT TO PROVIDE HIS LICENSE NUMBER ON THE TITLE |
| BLOCK AS REQUIRED BY SEC. 61G1-16.004 FLORIDA |
| ADMINISTRATIVE CODE AND CHAPTER 481 FLORIDA STATUTE. |
| |
| 9- VALUATION AND NUMBER OF SHEETS WERE UPDATED. OWES |
| $692.85. |
| |
| 10- SPECIFY ON PLANS CARBON MONOXIDE ALARMS IN ALL |
| BEDROOMS AS REQUIRED BY SEC. R313.4. |
| |
| 11- A) PLEASE SPECIFY OVERFLOW SCUPPERS AS REQUIRED BY |
| SEC. R903.4.1. |
| |
| B) ROOF SCUPPERS SHOWN ON PLANS AND ELEVATIONS DON'T |
| SHOW ANY DOWNSPOUTS. PLEASE PROVIDE SPECIFICATIONS |
| SHOWING HOW PROTECTING THE BUILDING AS REQUIRED BY SEC. |
| R320.7. |
| |
| C) PLEASE COORDINATE ROOF DRAINS AND SCUPPERS WITH |
| ENGINEER NOTE #1 ON DETAIL 1/S1 ON SHEET S-1. |
| |
| 12- PLEASE PROVIDE COMPLETE SPECIFICATIONS/DETAILS |
| SHOWING COMPLIANCE WITH THE ROOF VENTILATION AS |
| REQUIRED BY SEC. R806. |
| |
| 13- SHEET A-0: PLEASE REVISE FRAMING NOTE #9. MAXIMUM |
| RISER HEIGHT SHALL BE 7-3/4" NO 8". SEC. R311.5.3.1 |
| |
| 14- SHEET A-1: PLEASE COORDINATE NEW ENTRY STEPS WITH |
| INFORMATION SHOWN ON FOUNDATION PLAN ON SHEET S-1. AND |
| PROVIDE RISER AND TREAD DIMENSIONS TO VERIFY COMPLIANCE |
| WITH SEC. R311.5.3. |
| ALSO, PROVIDE DIMENSIONS FOR STEPS AND LANDING AT REAR |
| DOOR BY THE KITCHEN AREA AND AT THE NEW LOGGIA. |
| |
| 15- SHEET A-2: PLEASE CLARIFY ROOF SPECIFICATIONS ON |
| DETAIL 1 AND DETAIL 2. INFORMATION PROVIDED IS |
| CONFUSING THE UNDERLAYMENT WITH THE SHEATHING. CLEARLY |
| IDENTIFY UNDERLAYMENT NAIL TYPE AND SPACING (SEE FLAT |
| ROOF PRODUCT APPROVAL) AND ROOF SHEATHING NAIL TYPE AND |
| SPACING. STRUCTURAL DRAWINGS ARE MISSING THE |
| SPECIFICATIONS FOR THE ROOF SHEATHING AND THE TERRACE |
| SHEATHING. **NOTE: SEC. R803.2.3.1 REQUIRES 8D RING |
| SHANK NAILS AND ROOF ZONE 3 NEED TO BE AT 4"O.C.. |
| PLEASE PROVIDE COMPLETE SPECIFICATIONS, INCLUDING THE |
| ROOF SHEATHING THICKNESS, NAIL SIZE AND SPACING IN THE |
| STRUCTURAL DRAWINGS. |
| |
| 16- SHEET S-1: A) THE SLOPE REQUIRED FOR ALL FLAT ROOFS |
| IS 1/4" PER FOOT MINIMUM. SEC. R905.11.1. PLANS AND |
| SECTIONS SHOW 2" SLOPE. THIS DOESN'T PROVIDE THE |
| REQUIRED MINIMUM SLOPE. REVISE ALL SPECIFICATIONS ON |
| PLANS AND DETAILS AS REQUIRED. |
| |
| B) DETAIL 1/S1 SPECIFIES 3/4" STUCCO. NEED TO PROVIDE |
| 7/8" MIN. AS REQUIRED BY TABLE R702.1(1). PLEASE REVISE |
| AS REQUIRED. |
| |
| C) PLEASE PROVIDE SPECIFICATIONS FOR COLUMNS AND |
| HEADERS ON THE WIDENED OPENING BY THE BUTLER'S PANTRY |
| AND THE RELOCATED BACK DOOR IN THE KITCHEN AREA. SEC. |
| R301. |
| |
| D) PLEASE REVISE NOTE #1 ON DETAIL 2/S1. SEE SEC. |
| R319.1 FOR DISTANCE FROM GRADE AND REVISE AS REQUIRED. |
| |
| E) PLEASE REVISE NOTE #3 ON DETAIL 2/S1. SEE SEC. R408 |
| FOR MINIMUM REQUIREMENTS AND COORDINATE WITH |
| ARCHITECTURAL PLANS ALSO. |
| |
| 17- SHEET S-2: PLEASE REVISE ALL SPECIFICATIONS ON |
| PLANS AND DETAILS THAT REFER TO THE ROOF SLOPE. SEE |
| ITEM 16(A) ABOVE. |
| |
| 18- SHEET S-3: SAME COMMENT AS #17 APPLIES. |
| |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |