2011-11-18 17:04:16ADDITION/REVISION BUILDING REVIEW COMMENTS.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PLEASE PROVIDE ENERGY CALCULATIONS AS REQUIRED BY
 SEC. N1100.3.
  
 2- PLEASE PROVIDE PRODUCT APPROVAL (2 COPIES) AS
 REQUIRED BY DCA RULE 9N-3 FOR:
 A) CASEMENT WINDOWS AS SPECIFIED ON PLANS.
 B) SINGLE HUNG WINDOWS. NOA 11-0405.10 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE. PLEASE VISIT THE MIAMI-DADE
 WEBSITE AND DOWNLOAD CURRENT NOA.
 C) FIBERGLASS EXTERIOR DOOR. FLORIDA PRODUCT APPROVAL
 FL-11321.6 SUBMITTED IS FOR 8'-0" DOORS. NEED ONE FOR
 6'-8" DOORS AS SPECIFIED ON PLANS.
 D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS, SECTIONS AND UPLIFT CONNECTOR SCHEDULE. PLEASE,
 PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL COVER PAGE
 AND PAGE SHOWING THE SPECIFIED CONNECTOR.
 E) WINDOW MULLIONS AS SHOWN ON PLANS. AND CLEARLY
 INDICATE SIZE OF MULLION TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.2.1.4.3.
 F) FLAT ROOF. AND, CLEARLY IDENTIFY WHICH APPROVED
 ASSEMBLY IS GOING TO BE INSTALLED AND PROVIDE RAS 117
 CALCULATIONS. CALCULATIONS TO BE SIGNED AND SEALED IF
 THE PRODUCT APPROVAL SUBMITTED REQUIRES IT.
  
 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS PRIOR
 TO SUBMITTAL TO THIS OFFICE AS REQUIRED BY SEC. 106.3.3
 CITY AMENDMENTS TO FBC.
  
 4- PLEASE HAVE ALL THE REVISED PLANS AND PRODUCT
 APPROVALS REVIEWED BY HISTORIC FOR APPROVAL PRIOR TO
 SUBMITTAL TO THIS OFFICE.
  
 5- PLEASE PROVIDE STORM SHUTTERS COMPLETE INSTALLATION
 SCHEDULE. AND, CLEARLY MARK ON SHUTTERS DRAWINGS
 SPECIFIC WALL MOUNTING CONDITIONS (EX: WALL MOUNTED
 SECTION 1 OR WALL MOUNTED SECTION 2, ETC.), ANCHOR TYPE
 AND SPACING TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES BY SEC. R301.2.1.4.3.
  
 6- PLEASE BRING REVISED PLANS TO PALM BEACH COUNTY TO
 VERIFY IF IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS
 AND COPY OF PAID RECEIPT IF FEES ARE DUE.
  
 7- PLEASE SPECIFY TYPE OF EXISTING BEDROOM WINDOWS TO
 BE REPLACED (EX: CASEMENT, SINGLE HUNG, ETC) TO VERIFY
 COMPLIANCE WITH THE EGRESS REQUIREMENTS OF SEC. R310.
  
 8- ARCHITECT TO PROVIDE HIS LICENSE NUMBER ON THE TITLE
 BLOCK AS REQUIRED BY SEC. 61G1-16.004 FLORIDA
 ADMINISTRATIVE CODE AND CHAPTER 481 FLORIDA STATUTE.
  
 9- VALUATION AND NUMBER OF SHEETS WERE UPDATED. OWES
 $692.85.
  
 10- SPECIFY ON PLANS CARBON MONOXIDE ALARMS IN ALL
 BEDROOMS AS REQUIRED BY SEC. R313.4.
  
 11- A) PLEASE SPECIFY OVERFLOW SCUPPERS AS REQUIRED BY
 SEC. R903.4.1.
  
 B) ROOF SCUPPERS SHOWN ON PLANS AND ELEVATIONS DON'T
 SHOW ANY DOWNSPOUTS. PLEASE PROVIDE SPECIFICATIONS
 SHOWING HOW PROTECTING THE BUILDING AS REQUIRED BY SEC.
 R320.7.
  
 C) PLEASE COORDINATE ROOF DRAINS AND SCUPPERS WITH
 ENGINEER NOTE #1 ON DETAIL 1/S1 ON SHEET S-1.
  
 12- PLEASE PROVIDE COMPLETE SPECIFICATIONS/DETAILS
 SHOWING COMPLIANCE WITH THE ROOF VENTILATION AS
 REQUIRED BY SEC. R806.
  
 13- SHEET A-0: PLEASE REVISE FRAMING NOTE #9. MAXIMUM
 RISER HEIGHT SHALL BE 7-3/4" NO 8". SEC. R311.5.3.1
  
 14- SHEET A-1: PLEASE COORDINATE NEW ENTRY STEPS WITH
 INFORMATION SHOWN ON FOUNDATION PLAN ON SHEET S-1. AND
 PROVIDE RISER AND TREAD DIMENSIONS TO VERIFY COMPLIANCE
 WITH SEC. R311.5.3.
 ALSO, PROVIDE DIMENSIONS FOR STEPS AND LANDING AT REAR
 DOOR BY THE KITCHEN AREA AND AT THE NEW LOGGIA.
  
 15- SHEET A-2: PLEASE CLARIFY ROOF SPECIFICATIONS ON
 DETAIL 1 AND DETAIL 2. INFORMATION PROVIDED IS
 CONFUSING THE UNDERLAYMENT WITH THE SHEATHING. CLEARLY
 IDENTIFY UNDERLAYMENT NAIL TYPE AND SPACING (SEE FLAT
 ROOF PRODUCT APPROVAL) AND ROOF SHEATHING NAIL TYPE AND
 SPACING. STRUCTURAL DRAWINGS ARE MISSING THE
 SPECIFICATIONS FOR THE ROOF SHEATHING AND THE TERRACE
 SHEATHING. **NOTE: SEC. R803.2.3.1 REQUIRES 8D RING
 SHANK NAILS AND ROOF ZONE 3 NEED TO BE AT 4"O.C..
 PLEASE PROVIDE COMPLETE SPECIFICATIONS, INCLUDING THE
 ROOF SHEATHING THICKNESS, NAIL SIZE AND SPACING IN THE
 STRUCTURAL DRAWINGS.
  
 16- SHEET S-1: A) THE SLOPE REQUIRED FOR ALL FLAT ROOFS
 IS 1/4" PER FOOT MINIMUM. SEC. R905.11.1. PLANS AND
 SECTIONS SHOW 2" SLOPE. THIS DOESN'T PROVIDE THE
 REQUIRED MINIMUM SLOPE. REVISE ALL SPECIFICATIONS ON
 PLANS AND DETAILS AS REQUIRED.
  
 B) DETAIL 1/S1 SPECIFIES 3/4" STUCCO. NEED TO PROVIDE
 7/8" MIN. AS REQUIRED BY TABLE R702.1(1). PLEASE REVISE
 AS REQUIRED.
  
 C) PLEASE PROVIDE SPECIFICATIONS FOR COLUMNS AND
 HEADERS ON THE WIDENED OPENING BY THE BUTLER'S PANTRY
 AND THE RELOCATED BACK DOOR IN THE KITCHEN AREA. SEC.
 R301.
  
 D) PLEASE REVISE NOTE #1 ON DETAIL 2/S1. SEE SEC.
 R319.1 FOR DISTANCE FROM GRADE AND REVISE AS REQUIRED.
  
 E) PLEASE REVISE NOTE #3 ON DETAIL 2/S1. SEE SEC. R408
 FOR MINIMUM REQUIREMENTS AND COORDINATE WITH
 ARCHITECTURAL PLANS ALSO.
  
 17- SHEET S-2: PLEASE REVISE ALL SPECIFICATIONS ON
 PLANS AND DETAILS THAT REFER TO THE ROOF SLOPE. SEE
 ITEM 16(A) ABOVE.
  
 18- SHEET S-3: SAME COMMENT AS #17 APPLIES.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712