2011-11-15 10:49:28FBC 2007 PLUMBING REVIEW #1
 DENIED:
  
 1. OCCUPANCY GROUP AND OCCUPANT COUNT NEED TO BE
 DETERMINED SO THAT A FIXTURE COUNT CAN BE DETERMINED.
 1A. IF OCCUPANCY IS ASSEMBLY A SERVICE SINK WILL BE
 REQUIRED. PLUMBING TABLE 403.1
 1B. SHEET A-2.THE RESTROOM/ SHOWER ROOMS DO NOT
 INDICATE COMPLIANCE WITH 11-4.21 SHOWER STALLS.
 1C. SHEET A-2 THE ADA TOILET STALLS DO NOT APPEAR TO
 COMPLY WITH 11-4.17.3 SIZE AND ARRANGEMENT (EXCEPTION)
 SEE FIGURE 30(E) THE REQUIRED WIDTH WOULD BE A MINIMUM
 OF 7'-1" CLEAR.
  
 2. FLOOR DRAINS REQUIRE TRAP PRIMERS. PLUMBING 1002.4
  
 3. PLEASE INCLUDE IN THE WATER PIPE DRAWING THE WATER
 HEATER RELIEF AND PAN DRAIN PIPE AND TERMINATION PER
 504.6 AND 504.7.2
 3A PLEASE INCLUDE THE REQUIRED WATER SHUTOFF VALVES ON
 THE WATERPIPE DRAWING. 606.1 LOCATION OF FULL-OPEN
 VALVES. FULL-OPEN VALVES SHALL BE INSTALLED IN THE
 FOLLOWING LOCATIONS:
 ON THE WATER DISTRIBUTION SUPPLY PIPE AT THE ENTRANCE
 INTO THE STRUCTURE.
 ON THE WATER SUPPLY PIPE TO EVERY WATER HEATER.
  
 4. PER CITY OF WEST PALM BEACH BACKFLOW AND
 CROSS-CONNECTION CONTROL POLICY AN RPZ BACKFLOW
 PREVENTER IS REQUIRED AS CLOSE AS POSSIBLE TO THE WATER
 METER ON PRIVATE PROPERTY.
  