Plan Review Notes For Permit 11110076 |
Permit Number |
11110076 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-11-15 10:49:28 | FBC 2007 PLUMBING REVIEW #1 | | DENIED: | | | | 1. OCCUPANCY GROUP AND OCCUPANT COUNT NEED TO BE | | DETERMINED SO THAT A FIXTURE COUNT CAN BE DETERMINED. | | 1A. IF OCCUPANCY IS ASSEMBLY A SERVICE SINK WILL BE | | REQUIRED. PLUMBING TABLE 403.1 | | 1B. SHEET A-2.THE RESTROOM/ SHOWER ROOMS DO NOT | | INDICATE COMPLIANCE WITH 11-4.21 SHOWER STALLS. | | 1C. SHEET A-2 THE ADA TOILET STALLS DO NOT APPEAR TO | | COMPLY WITH 11-4.17.3 SIZE AND ARRANGEMENT (EXCEPTION) | | SEE FIGURE 30(E) THE REQUIRED WIDTH WOULD BE A MINIMUM | | OF 7'-1" CLEAR. | | | | 2. FLOOR DRAINS REQUIRE TRAP PRIMERS. PLUMBING 1002.4 | | | | 3. PLEASE INCLUDE IN THE WATER PIPE DRAWING THE WATER | | HEATER RELIEF AND PAN DRAIN PIPE AND TERMINATION PER | | 504.6 AND 504.7.2 | | 3A PLEASE INCLUDE THE REQUIRED WATER SHUTOFF VALVES ON | | THE WATERPIPE DRAWING. 606.1 LOCATION OF FULL-OPEN | | VALVES. FULL-OPEN VALVES SHALL BE INSTALLED IN THE | | FOLLOWING LOCATIONS: | | ON THE WATER DISTRIBUTION SUPPLY PIPE AT THE ENTRANCE | | INTO THE STRUCTURE. | | ON THE WATER SUPPLY PIPE TO EVERY WATER HEATER. | | | | 4. PER CITY OF WEST PALM BEACH BACKFLOW AND | | CROSS-CONNECTION CONTROL POLICY AN RPZ BACKFLOW | | PREVENTER IS REQUIRED AS CLOSE AS POSSIBLE TO THE WATER | | METER ON PRIVATE PROPERTY. | | | | REVIEW BY | | LARRY WAGNER | | CHIEF PLUMBING INSPECTOR | | PHONE # 805-6692 | | EMAIL [email protected] | | FAX # 805-6676 | | | | |
|