2011-11-08 13:19:14 | 1016 CLARE AVENUE - SUITE #7 |
| PERMIT #11110076 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS |
| OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE |
| REMOVED FROM THE SITE DAILY. |
| |
| FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF |
| THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY. |
| |
| PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| |
| EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS |
| SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A |
| CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM. |
| SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF |
| OCCUPANTS PERMITTED FOR EACH ROOM. |
| |
| PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY |
| RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING |
| NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM |
| WWW.KNOXBOX.COM. |
| |
| PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET. |
| NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT |
| LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND SHALL |
| CONTRAST THE BACKGROUND. |
| |
| INDICATE NEW AND EXISTING EMERGENCY LIGHTING. |
| |
| PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| EXIT SIGNS. |
| |
| FOR OCCUPANCIES WITH AN OCCUPANT LOAD OF 100 OR MORE |
| PERSONS, PANIC HARDWARE SHALL BE PROVIDED ON DOORS TO |
| RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR LATCHES ARE |
| PERMITTED THAT WOULD NOT BE RELEASED BY THE PANIC |
| HARDWARE. AS A SUBSTITUTE FOR PANIC HARDWARE, THE MAIN |
| ENTRANCE IS PERMITTED TO HAVE AN INTERIOR KEYED DOOR |
| LOCK (AND NO LATCH) WITH A READILY VISIBLE SIGN STATING |
| THIS DOOR TO REMAIN UNLOCKED WHEN THE BUILDING IS |
| OCCUPIED. SIGN LETTERS SHALL BE AT LEAST 1 INCH IN |
| HEIGHT. A THUMB TURN STYLE LOCK IS NOT PERMITTED TO BE |
| SUBSTITUTED FOR A KEYED LOCK. |
| |
| DOORS ARE REQUIRED TO SWING IN THE DIRECTION OF EGRESS |
| TRAVEL FOR AN OCCUPANT LOAD OF 50 OR GREATER PERSONS. |
| |
| SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE |
| MODIFICATION OF THE FIRE SPRINKLER SYSTEM. FIRE |
| SPRINKLER SYSTEM TO BE SUPERVISED BY A MONITORING |
| COMPANY. SPRINKLERS SHALL BE LOCATED ABOVE AND BELOW |
| CEILING SPACES THAT ARE NOT CONCEALED. |
| |
| WESLEY JOLIN |
| WEST PALM BEACH FIRE RESCUE |
| FIRE & LIFE SAFETY PLAN REVIEW |
| |