2011-11-08 09:40:2111110076
 1016 CLARE AVE #7
 INTERIOR BUILD OUT
  
 SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE
 CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES
 AS REQUIRED BY THE FLORIDA BUILDING CODE. SPACE CONTROL
 FBC 13-415 ABC.1.2; ADDITIONAL CONTROLS 13-415.ABC.1.3,
 EXISTING BUILDING 711.1
 PROVIDE A LIGHTING DENSITY CALCULATION SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC 13-415 ABC.5
 ELECTRICAL FEEDERS TO BAY 1 AND 2 IMPROPERLY SIZED. NEC
 TABLE 310-16, 215.5
 PROVIDE AN ELECTRICAL LOAD CALCULATION FOR BOTH PANELS.
 NEC 215.5
 GFCI PROTECTION REQUIRED FOR RECEPTACLES IN BATHROOMS,
 OUTDOORS, ROOFTOPS AND ADJACENT TO SINKS. NEC 210.8
 PROVIDE SPECIFICATIONS ON LIGHT FIXTURES. LUMINAIRES
 SUBJECT TO PHYSICAL DAMAGE INSTALLED IN PLAYING AREAS
 AND SPECTATOR SEATING AREAS SHALL BE PROTECTED FROM
 DAMAGE. NEC 410.10(E)
 VERIFY THAT ALL MAIN SERVICE DISCONNECTS ARE GROUPED IN
 ONE LOCATION. SHOW SERVICE LOCATION ON THE PLAN. NEC
 230.72
 PROVIDE A DETAIL SHOWING THAT THE REQUIRED WORKING
 CLEARANCES AND DEDICATED WORKING SPACE HAS BEEN
 PROVIDED FOR THE ELECTRICAL EQUIPMENT. NEC 110.26,
 240.24, 408.17\
 LOCATE THE AIR CONDITIONING EQUIPMENT ON THE PLAN.
 PROVIDE A GFCI PROTECTED RECEPTACLE WITHIN 25 FEET OF
 ALL HEATING, AND AIR CONDITIONING FOR SERVICING OF THE
 EQUIPMENT. NEC 210.63
  