2011-11-10 14:14:18 | BUILDING PLAN REVIEW |
| PERMIT: 11110076 |
| ADD: 1016 CLARE AVE |
| CONT: TRI R CONSTRUCTION COMPANY |
| TEL: (772)336-6444 |
| |
| 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) THESE ARE MINIMUMS FOR COMMERCIAL BUILDING REVIEW. |
| 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| BUILDING: |
| |
| 1A) OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS |
| SHALL BE DETERMINED. |
| |
| 1B). MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED |
| (SEE TABLE 503). |
| |
| |
| 1C) FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL |
| INCLUDE THE FOLLOWING COMPONENTS: |
| FIRE-RESISTANT SEPARATIONS |
| FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION |
| PROTECTION OF OPENINGS AND PENETRATIONS OF RATED WALLS |
| FIRE BLOCKING AND DRAFTSTOPPING AND CALCULATED FIRE |
| RESISTANCE |
| |
| 1D) LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL |
| INCLUDE THE FOLLOWING REQUIREMENTS: |
| OCCUPANT LOAD AND EGRESS CAPACITIES |
| |
| 1E) OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| OCCUPANCY LOAD |
| GROSS |
| NET |
| MEANS OF EGRESS |
| DOORS AMOUNT OF OCCUPANTS ALLOWED THROUGH EGRESS |
| DOORWAYS |
| EMERGENCY LIGHTING AND EXIT SIGNS |
| SPECIFIC OCCUPANCY REQUIREMENTS |
| |
| 2) PLANS SHEET A-2 DO NOT PROVIDE ENOUGH OCCUPANTS ON |
| THE SOCCER FIELDS, ARE NOT INDICATING LINESMEN, ETC. |
| ALONG THE SIDE LINES NO OCCUPANT LOAD HAS BEEN |
| ESTABLISHED SEE |
| FBC-B TABLE 1004.1.1 FOR OCCUPANT LOADS FOR SPECTATOR |
| WAITING AND SEATING AREA BY BAR. THERE IS ANOTHER AREA |
| TO THE RIGHT OF THE MAIN ENTRANCE APPROXIMATELY 45'X45' |
| WITH NO DESINATION OF USAGE, NOR OCCUPANT LOAD. 106.1.2 |
| ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 3) SHEET A-2.THE RESTROOM/ SHOWER ROOMS DO NOT INDICATE |
| COMPLIANCE WITH 11-4.21 SHOWER STALLS NOR DRESSING |
| ROOMS. |
| |
| 4) SHEET A-2 THE DOUBLE DOORS LOCATED BETWEEN THE MAIN |
| ENTRY LOBBY AND WAITING/ SEATING AREA SWING THE WRONG |
| WAY, WITH OCCUPANT LOADS 50 AND GREATER SWING IN THE |
| DIRECTION OF EXIT TRAVEL, FBC-B 1008.1.2. |
| |
| 5) A-2) PLEASE PROVIDE ON THE LIFE SAFETY PLAN THE |
| LOCATION FOR TABLE & CHAIRS, IF BLEACHERS WILL BE |
| INSTALLED? IF SO OF WHAT TYPE MATERIALS? HOW HIGH OF |
| TIERS? ACCESSIBILITY? |
| |
| 6) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |