2011-11-08 12:59:28 | 509 NORTHWOOD ROAD |
| PERMIT #11110070 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS |
| OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE |
| REMOVED FROM THE SITE DAILY. |
| |
| PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| |
| PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET. |
| NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT |
| LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND SHALL |
| CONTRAST THE BACKGROUND. |
| |
| PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| EXIT SIGNS. |
| |
| DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM THE |
| EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. LOCKS, |
| IF PROVIDED, SHALL NOT REQUIRE THE USE OF A KEY, TOOL, |
| OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE |
| EGRESS SIDE. |
| |
| THE RELEASING MECHANISM ON ALL DOORS SHALL OPEN THE |
| DOOR WITH NOT MORE THAN ONE RELEASING OPERATION. THE |
| RELEASING MECHANISM SHALL HAVE AN OBVIOUS METHOD OF |
| OPERATION THAT IS READILY OPERATED UNDER ALL LIGHTING |
| CONDITIONS. THE RELEASING DEVICE SHOULD BE CAPABLE OF |
| BEING OPERATED WITH ONE HAND AND SHOULD NOT REQUIRE |
| TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST |
| TO OPERATE. |
| |
| WESLEY JOLIN |
| WEST PALM BEACH FIRE RESCUE |
| FIRE & LIFE SAFETY PLAN REVIEW |
| |