2011-11-14 14:51:11 | BUILDING PLAN REVIEW |
| PERMIT: 11110070 |
| ADD: 509 NORTHWOOD ROAD |
| CONT: SHELL RAZOR'S INC. |
| TEL: (561)251-9718 |
| |
| 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1) IS THIS A CHANGE OF OCCUPANCY? |
| |
| 2) SHEET S-1 SECTION A-A INDICATES THE REMOVAL OF A |
| BLOCK WALL, SHORING UP A 8X12 4 BAR BEAM AND APPLYING A |
| 4X6 ANGLE TO THE BOTTOM OF THE BEAM. NOTES ALSO |
| INDICATE THE USE OF A 4"X4" STEEL COLUMN WITH A TOP AND |
| BOTTOM PLATE 7"X7". THE PLANS ARE NOT CLEAR AS TO HOW |
| THE STEEL ANGLE AND COLUMN ARE TO BE JOINED TOGETHER BY |
| BOLTING OR WELDING THE COLUMN TO THE STEEL ANGLE? IF |
| THE TWO ARE TO BE WELDED WHAT IS THE TYPE OF WELD, THIS |
| IS NOT KNOWN OF THE BOTTOM WELD? 106.1.2 ADDITIONAL |
| INFORMATION REQUIRED. |
| |
| 3) FOR THE SAME CONCRETE BEAM AND STEEL COLUMN |
| CONFIGURATION, WHERE THE BLOCK WALL WALL IS REMOVED, IS |
| THERE ANY PROVISIONS TO BE MADE HOW THE WEIGHT WILL BE |
| TRANSFERRED TO THE FOUNDATION BELOW? ARE THE BLOCK |
| CAVITIES TO BE FILLED ? ADDITIONAL INFORMATION |
| REQUIRED? |
| |
| 4) THE OTHER SECTION B-B IS FOR THE RAFTERS AND OR |
| CEILING JOIST. ARE THE EXISTING ROOF FRAMING MEMBERS |
| SPANNING THE 18'-2" CLEAR OR IS THERE A SPLICE OVER THE |
| EXISTING BEARING WALL THAT IS BEING REMOVED? IF THERE |
| IS A SPLICE OVER THE EXISTING BEARING WALL THE NEW |
| GLULAM BEAM IS OVER 3'-6" AWAY FROM THE SPLICE POINT? |
| ADDITIONAL INFORMATION REQUIRED? |
| |
| 5) THE NEW GLULAM BEAM IS TO BE 5 1/2"X 12" PLEASE |
| PROVIDE PRODUCT REPORT FOR WHICH HGUS HANGER YOU ENTEND |
| ON INSTALLING AND TO WHAT TYPE OF MATERIALS THIS HANGER |
| WILL BE ATTACHED TO. IT APPEARS THAT THE ONE END WILL |
| BE ATTACHING INTO THE 4X6 STEEL ANGLE. NOTE MOST |
| MANUFACTURERS OF HANGERS WILL VOID THE APPROVALS IF |
| THEY ARE WELDED AT ALL. |
| |
| 6) ARE THERE ANY FINSIHES BEING REPLACED, WALLS AND OR |
| CEILING? |
| |
| 7) S-1 INDICATES A NEW REAR DOOR LOCATION BUT THERE ARE |
| NO STRUCTURAL DETAILS INDICATING HOW THE MWFRS WILL |
| REMAIN , NO COLUMN, LENTAL DETAILS. MISSING WIND DESIGN |
| CRITERIA.FBC-B 1609. |
| |
| 8) EXISTING BUILDING CODE 808 MINIMUM REQUIREMENTS. |
| ALTERATIONS SUBJECT TO THIS CHAPTER SHALL COMPLY WITTH |
| THE REQUIREMENTS OF CHAPTER 13 FOR THE FBC-B. |
| |
| BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |