Plan Review Notes
Plan Review Notes For Permit 11110034
Permit Number 11110034
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2011-11-04 11:49:361041 45TH STREET - OAKWOOD AREA
 PERMIT #11110034
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO*****
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 PER LOCAL CODE AMENDMENTS, DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM CONDITION.
  
 INDICATE HOW THE EXISTING FIRE SPRINKLER SYSTEM FLOW
 SWITCH(ES) WILL BE TIED INTO THE NEW FIRE ALARM SYSTEM.
  
 PLANS INDICATE THE FIRE ALARM SYSTEM WILL BE UL LISTED
 UPON COMPLETION. UL WEBSITE DOES NOT CURRENTLY INDICATE
 A CERTIFICATE FOR THIS LOCATION AS BEING MONITORED FOR
 CENTRAL STATION SERVICE. PLEASE VERIFY.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  