Plan Review Notes
Plan Review Notes For Permit 11100715
Permit Number 11100715
Review Stop E
Sequence Number 1
Notes
Date Text
2011-11-09 16:26:0711100715
 223 PINE STREET
 OCCUPANCY CHANGE FROM RESIDENTIAL TO BUSINESS
  
 GARAGE REQUIRES A SUB PANEL FOR THE ELECTRICAL LOADS
 AND TO FACILITATE THE REQUIRED GROUNDING AND BONDING OF
 THE ELECTRICAL SYSTEM. NEC 250.32
  
 SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE
 CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES
 AS REQUIRED BY THE FLORIDA BUILDING CODE. SPACE CONTROL
 FBC 13-415 ABC.1.2; ADDITIONAL CONTROLS 13-415.ABC.1.3,
 EXISTING BUILDING 711.1
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  