Plan Review Notes For Permit 11100706 |
Permit Number |
11100706 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2011-10-31 12:22:53 | RE-ROOF BUILDING REVIEW CHECKLIST. | | 2007 FBC W/ 2007 REVISIONS. | | | | 1- RE-ROOF NEED TO HAVE MINIMUM THE SAME INSULATION | | R-VALUE THAT WAS ON EXISTING BUILDING. SEC. 601.2 FBC | | 2007-EXISTING BUILDING CODE. RE-ROOF SYSTEM NEEDS TO BE | | ONE WITH INSULATION. | | | | 2- CLEARLY IDENTIFY WHICH SYSTEM FROM PAGE 8 OF 17 OF | | NOA SUBMITTED IS GOING TO BE INSTALLED TO VERIFY | | COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. 1609 FBC. | | | | 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO | | LOW. SEC. 108.3 CITY AMENDMENTS TO FBC. | | | | 4- FOR YOUR INFORMATION: | | A) ANY ROOF EQUIPMENT REMOVAL REQUIRES SEPARATE PERMIT. | | | | B) ANY ROOF DRAINS RETROFIT REQUIRE PLUMBING REVIEW. | | | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|