2011-11-08 15:24:59BUILDING PROVISO:
  
 1) SHEET A.02. DOOR # 1 AND WALL SECTIONS COMMON TO
 STAIRWELL # 1, 1 HOUR RATED. FBC-B 1020.1.
  
  
 2) SHEET A.02. DOOR# 15 REQUIRES 18" CLEAR LATCH SIDE
 OF DOOR SEE 2007/09 FBC-B 11-4.13.6
  
 3) SHEET A.04. CORNER SINK DETAIL:
 11-4.24.2 SINKS SHALL BE MOUNTED WITH THE COUNTER OR
 RIM NO HIGHER THAN 34 INCHES ABOVE THE FINISH FLOOR.
  
 11-4.24.5 SECTION 11-4.2.4 (CLEAR FLOOR SPACE) SHAL BE
 PROVIDED IN FRONT OF SINKS TO ALLOW FORWARD APPROACH.
  