Plan Review Notes
Plan Review Notes For Permit 11100678
Permit Number 11100678
Review Stop B
Sequence Number 1
Notes
Date Text
2011-10-28 13:59:58RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW CHECKLIST.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PROVIDE ALL THE INFORMATION REQUIRED BY THE CITY
 POLICY FOR RE-ROOFING PERMITS:
 A) SPECIFY HOW MUCH ROOF AREA IS FOR FLAT ROOF AND HOW
 MUCH AREA IS FOR SHINGLES.
  
 B) SPECIFY ROOF MEAN ROOF HEIGHT.
  
 C) SPECIFY ROOF PITCH.
  
 2- FLAT ROOF PRODUCT APPROVALS SUBMITTED:
  
 A) PROVIDE FLORIDA PRODUCT APPROVAL COVER PAGE AND THE
 FIRST PAGES SHOWN THE GENERAL NOTES THAT APPLY. ALSO,
 PROVIDE PAGE SHOWING THE SPECIFIC ASSEMBLY TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.2.1.4.3. INFORMATION SUBMITTED
 IS INCOMPLETE AND MIS-MATCHING UNDERLAYMENT PRODUCT
 APPROVAL WITH FLAT ROOF ASSEMBLIES PRODUCT APPROVAL.
  
 B) PAGE 9 OF 30 OF FLORIDA PRODUCT APPROVAL FL1654-R9
 SUBMITTED INDICATES THE PROPOSED INSTALLATION SYSTEM NO
 W-33. THIS SYSTEM ASSEMBLY IS GOOD FOR A DESIGN
 PRESSURE OF -97.5 PSF. THIS IS A BONDED ROOF SYSTEM AND
 IT DOESN'T ALLOW NAIL ENHANCING (SEE NOTE #9 ON
 FL1654-R9). ACCORDING TO THE FLORIDA RESIDENTIAL CODE
 2009 REVISIONS SEC. R301.2.1.4.3 THIS BUILDING IS
 LOCATED ON EXPOSURE "C". THE DESIGN PRESSURES FOR
 EXPOSURE C ARE HIGHER THAN -97.5PSF AT THE CORNER
 AREAS. THEREFORE, THIS SYSTEM CAN'T BE USED. NEED TO
 SELECT ANOTHER SYSTEM THAT MEETS THE DESIGN PRESSURES
 FOR EXPOSURE C.
  
 ***NOTE: MECHANICALLY ATTACHED BASE SHEET SYSTEMS
 ALLLOW NAIL ENHANCING CALCULATIONS. IF USING A
 MACHANICALLY ATTACHED SYSTEM THEN PROVIDE SIGNED AND
 SEALED RAS 117 CALCULATIONS AS REQUIRED BY NOTE #8 ON
 FLORIDA PRODUCT APPROVAL FL1654-R9.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  
  