2011-11-16 08:59:30PLANS DENIED
 1) PAGE A-2 ON THE PLANS SHOWS UNISEX BATHROOM WITH
 1HR.RATED PARTITION.
 REFER TO SECTION 607.5.3 2007 FBC(M)
 2) PAGE M-1 RETURN AIR IS NOT REQUIRED IN BATHROOM PER
 SECTION 601.4 EXCEPTION 3.
 EXHAUST IS REQUIRED PER TABLE 403.3 2007 FBC(M) .
 3) PLEASE PROVIDE A RETURN AIR DUCT LAYOUT ON THE
 PLANS.
 4) REFER TO SECTION 602.2.1 MATERIALS EXPOSED WITHIN
 PLENUMS 2007 FBC(M)