Plan Review Notes
Plan Review Notes For Permit 11100668
Permit Number 11100668
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2011-12-01 10:53:53716 NORTH SAPODILLA AVENUE
 PERMIT #11100668
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY.
  
 STORAGE OCCUPANCIES SHALL BE SEPARATED FROM MERCANTILE
 OCCUPANCIES WITH A 2-HOUR FIRE RATED BARRIER. ALL
 OPENINGS AND PENETRATIONS SHALL BE PROTECTED.
  
 EXTINGUISHERS SHALL HAVE A MINIMUM RATING OF 2A:10BC
 AND SHALL BE TAGGED BY A LICENSED FIRE EXTINGUISHER
 COMPANY.
  
 DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM THE
 EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. LOCKS,
 IF PROVIDED, SHALL NOT REQUIRE THE USE OF A KEY, TOOL,
 OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE
 EGRESS SIDE. THE LOCK/LATCH RELEASING MECHANISM ON ALL
 DOORS SHALL OPEN THE DOOR WITH NOT MORE THAN ONE
 RELEASING OPERATION. THE RELEASING MECHANISM SHALL HAVE
 AN OBVIOUS METHOD OF OPERATION THAT IS READILY OPERATED
 UNDER ALL LIGHTING CONDITIONS. THE RELEASING DEVICE
 SHOULD BE CAPABLE OF BEING OPERATED WITH ONE HAND AND
 SHOULD NOT REQUIRE TIGHT GRASPING, TIGHT PINCHING OR
 TWISTING OF THE WRIST TO OPERATE.
  
 EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER.
  
 PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL
 BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE.
  
 NOTE: ONLY ONE EXIT DOOR IS REQUIRED FOR CLASS C
 MERCANTILE OCCUPANCIES HAVING A COMMON PATH OF TRAVEL
 OF 75 FEET OR LESS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  