2011-10-31 12:58:24 | 11100668 | | 716 N. SAPODILLA | | QUEEN OF SHEEBA, LLC | | | | EQUIPMENT INTENDED TO INTERRUPT CURRENT AT FAULT LEVELS | | SHALL HAVE AN INTERRUPTING RATING SUFFICIENT FOR THE | | NOMINAL CIRCUIT VOLTAGE AND CURRENT THAT IS AVAILABLE | | AT THE LINE TERMINALS OF THE EQUIPMENT. PROVIDE | | INFORMATION FROM THE UTILITY ( FPL) ON THE AVAILABLE | | FAULT CURRENT. NEC 110.9 | | VERIFY THE EXISTING SERVICE RISER HAS ADEQUATE SIZE AND | | CLEARANCE. NEC 230.24 | | INDICATE THE WIRE SIZE REQUIRED FOR THE SERVICE RISER. | | NEC 310.16 | | VERIFY THAT ALL MAIN SERVICE DISCONNECTS ARE GROUPED IN | | ONE LOCATION. SHOW SERVICE LOCATION ON THE PLAN. NEC | | 230.72 | | MINIMUM 2? CONDUIT IS REQUIRED FOR 2/0 FEEDERS WITH | | GROUND. NEC 352.22 | | SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE | | CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES | | AS REQUIRED BY THE FLORIDA BUILDING CODE. SPACE CONTROL | | FBC 13-415 ABC.1.2; ADDITIONAL CONTROLS 13-415.ABC.1.3, | | EXISTING BUILDING 711.1 | | PROVIDE A BONDING BAR AT THE SERVICE. NEC 250-94 | | PROVIDE A 20 AMP RATED BRANCH CIRCUIT FOR A SIGN. NEC | | 600.5 | | INCLUDE WATER HEATING IN LOAD CALCULATION. NEC 220.40 | | TOTAL SERVICE LOAD SHOULD INCLUDE PANEL A. NEC 220.40 | | | | ROBERT LECKY | | COMMERCIAL COMBINATION PLANS EXAMINER | | [email protected] | | 561-805-6718 | | |
|