 716 N. SAPODILLA
 QUEEN OF SHEEBA, LLC
  
 EQUIPMENT INTENDED TO INTERRUPT CURRENT AT FAULT LEVELS
 SHALL HAVE AN INTERRUPTING RATING SUFFICIENT FOR THE
 NOMINAL CIRCUIT VOLTAGE AND CURRENT THAT IS AVAILABLE
 AT THE LINE TERMINALS OF THE EQUIPMENT. PROVIDE
 INFORMATION FROM THE UTILITY ( FPL) ON THE AVAILABLE
 FAULT CURRENT. NEC 110.9
 VERIFY THE EXISTING SERVICE RISER HAS ADEQUATE SIZE AND
 CLEARANCE. NEC 230.24
 INDICATE THE WIRE SIZE REQUIRED FOR THE SERVICE RISER.
 NEC 310.16
 VERIFY THAT ALL MAIN SERVICE DISCONNECTS ARE GROUPED IN
 ONE LOCATION. SHOW SERVICE LOCATION ON THE PLAN. NEC
 230.72
 MINIMUM 2? CONDUIT IS REQUIRED FOR 2/0 FEEDERS WITH
 GROUND. NEC 352.22
 SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE
 CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES
 AS REQUIRED BY THE FLORIDA BUILDING CODE. SPACE CONTROL
 FBC 13-415 ABC.1.2; ADDITIONAL CONTROLS 13-415.ABC.1.3,
 EXISTING BUILDING 711.1
 PROVIDE A BONDING BAR AT THE SERVICE. NEC 250-94
 PROVIDE A 20 AMP RATED BRANCH CIRCUIT FOR A SIGN. NEC
 600.5
 INCLUDE WATER HEATING IN LOAD CALCULATION. NEC 220.40
 TOTAL SERVICE LOAD SHOULD INCLUDE PANEL A. NEC 220.40
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  