Plan Review Notes
Plan Review Notes For Permit 11100668
Permit Number 11100668
Review Stop B
Sequence Number 1
Notes
Date Text
2011-11-04 17:27:51****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. FBC EXISTING BUILDING 101.5, ALTERATIONS AND CHANGE
 OF OCCUPANCY TO COMPLY WITH ONE OF THE METHODS
 (PRESCRIPTIVE, WORK AREA, OR PERFORMANCE). PLEASE
 SELECT METHOD AND SHOW COMPLIANCE ON THE PLAN.
  
 2. A1 AND A2, DOOR SWING IS CHANGED ON AN EXISTING REAR
 DOOR. HOW DOES THIS AFFECT WIND RESISTANCE FOR THE
 DOOR?
  
 3. PROVIDE PRODUCT APPROVALS FOR THE PROPOSED NEW DOORS
 AND WINDOWS, FAC9N-3.
  
 4. INCLUDE OCCUPANT LOAD ON THE LIFE SAFETY PLAN,
 FBC1004.
  
 5. A3, DESIGN PRESSURES APPEAR TOO LOW FOR EXPOSURE C,
 SEE FBC 1609 AND ASCE7-05.
  
 6. DOOR 4 (NOT SHOWN AS RATED) IS LOCATED IN A FIRE
 RATED WALL, SEE FBC 715.4.
  
 7. ENERGY CALCS REQUIRED, FBC 13-101.4.1.2.
  