2011-11-03 09:40:1511100654
 1704 FLORIDA AVE.
 INTERIOR RENOVATION
  
 ADD SMOKE ALARMS AND CARBON MONOXIDE ALARMS. FBC R313
 ALL NEW BRANCH CIRCUITS MUST BE PROTECTED WITH ARC
 FAULT CIRCUIT INTERRUPTERS. NEC 210.12
 NEW RECEPTACLES MUST BE TAMPER RESISTANT NEC 406.11
 A BONDING STRIP IS REQUIRED AT SERVICE GROUND NEC
 250.94
 THE SITE PLAN SHOWS A GARAGE. IF THE SCOPE OF
 RECONSTRUCTION INCLUDES AN ELECTRICAL CONNECTION TO THE
 GARAGE FROM THE HOUSE THAN A SPECIFIC WIRING METHOD IS
 REQUIRED. NEC 250.32
  