2012-01-20 12:56:21 | BUILDING PLAN REVIEW |
| PERMIT: 11100642 |
| ADD: 946 BELVEDERE RD |
| CONT: CONSTRUCTION REMODELING 1 |
| TEL: (561)667-9924 |
| |
| 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| |
| BUILDING APPROVED WITH EXCEPTION! |
| |
| THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| |
| BUILDING COMMENTS: |
| 1) THE WEST DOOR WILL NEED TO BE BLOCKED IN, A UNITY OF |
| TITLE DID NOT OCCUR FOR THE WEST SIDE OF THE BUILDING. |
| OPENINGS CAN NOT OCCUR ON ZERO LOT LINES PER 2007/09 |
| FBC-B TABLE 602. |
| |
| 2) WINDOW REPLACEMENT: CONTRACTOR TO SUBMIT PRODUCT |
| APPROVALS FOR THE REPLACEMENT WINDOWS BEFORE THE BUCK |
| INSPECTION CAN OCCUR. NOTE IF WINDOWS ARE NOT LARGE |
| MISSILE IMPACT RESISTANT TESTED THEN STORM SHUTTER |
| APPROVALS WILL ALSO NEED TO BE SUBMITTED FOR CODE |
| COMPLIANCE. |
| |
| MECHANICAL REVIEW: |
| 01/20/2012 OWNERS REPRESENTATIVE ROSE PHILYAW |
| (561-574-2300) REQUEST MECHANICAL BE STRUCK AND |
| MECHANICAL CONTRACTOR WILL COME IN UNDER SEPARATE |
| PERMIT WITH PLANS AND PAY SEPARATE FEES. WE SPOKE WITH |
| CBC MARK ROMMANELLI ABOUT HIS ISSUE. |
| |
| 1) LOUVER DOOR ON MECHANICAL CLOSET WILL NEED TO BE |
| METAL, RETURN AIR PLENUM IS THROUGH THE LOUVER DOOR. |
| 2007/09 FBC-M 602.2.1. |
| |
| 2) ROOF TOP CONDENSER WILL NEED PRODUCT APPROVALS TO BE |
| SUBMITTED WITH MECHANICAL PERMIT |
| |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |